4-way ceiling diffusers with fixed core and central screw mounting.
       
                      
        
 
Explanation
APW-4 = Diffuser type
444 = Diffuser size
 
Accessories (Optional)
REF = Plenum box
DSF = Volume control damper
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 | APW-4 294/150 | 145 x 145 |  | APW-4 369/225 | 220 x 220 |  | APW-4 444/300 | 295 x 295 |  | APW-4 519/375 | 370 x 370 |  | APW-4 595/445 | 445 x 445 |  
       
                                          Quick selection
    
      |
 |
 | Q | Ak | 0.0109 | 0.0244 | 0.0435 | 0.0679 | 0.0978 |  |
 | 100 |   | H= | 2.7 | 0.52 | 0.17 | 0.1 |   |   |   |   |   |   |   |   |   |   |   |   |  | Vz | H= | 3.2 | 0.2 | 0.11 | 0.08 |   |   |   |   |   |   |   |   |   |   |   |   |  |   | H= | 3.8 | 0.11 | 0.08 | 0.06 |   |   |   |   |   |   |   |   |   |   |   |   |  | Vk | 2.5 |   |   |   |   |  | X0,25 | 1.8 |   |   |   |   |  | Ps | 4 |   |   |   |   |  | Lw(A) | 22 |   |   |   |   |  | 150 |   | H= | 2.7 | 0.78 | 0.26 | 0.16 | 0.52 | 0.17 | 0.1 |   |   |   |   |   |   |   |   |   |  | Vz | H= | 3.2 | 0.29 | 0.17 | 0.12 | 0.2 | 0.11 | 0.08 |   |   |   |   |   |   |   |   |   |  |   | H= | 3.8 | 0.17 | 0.12 | 0.09 | 0.11 | 0.08 | 0.06 |   |   |   |   |   |   |   |   |   |  | Vk | 3.8 | 1.7 |   |   |   |  | X0,25 | 2.1 | 1.8 |   |   |   |  | Ps | 10 | 2 |   |   |   |  | Lw(A) | 32 | <20 |   |   |   |  | 200 |   | H= | 2.7 | 1.04 | 0.35 | 0.21 | 0.7 | 0.23 | 0.14 |   |   |   |   |   |   |   |   |   |  | Vz | H= | 3.2 | 0.39 | 0.22 | 0.16 | 0.26 | 0.15 | 0.1 |   |   |   |   |   |   |   |   |   |  |   | H= | 3.8 | 0.22 | 0.16 | 0.12 | 0.15 | 0.1 | 0.08 |   |   |   |   |   |   |   |   |   |  | Vk | 5.1 | 2.3 |   |   |   |  | X0,25 | 2.4 | 2 |   |   |   |  | Ps | 18 | 4 |   |   |   |  | Lw(A) | 39 | 22 |   |   |   |  | 300 |   | H= | 2.7 |   |   |   | 1.04 | 0.35 | 0.21 | 0.78 | 0.26 | 0.16 |   |   |   |   |   |   |  | Vz | H= | 3.2 |   |   |   | 0.39 | 0.22 | 0.16 | 0.29 | 0.17 | 0.12 |   |   |   |   |   |   |  |   | H= | 3.8 |   |   |   | 0.22 | 0.16 | 0.12 | 0.17 | 0.12 | 0.09 |   |   |   |   |   |   |  | Vk |   | 3.4 | 1.9 |   |   |  | X0,25 |   | 2.5 | 2.1 |   |   |  | Ps |   | 8 | 3 |   |   |  | Lw(A) |   | 32 | 20 |   |   |  | 400 |   | H= | 2.7 |   |   |   | 1.39 | 0.46 | 0.28 | 1.04 | 0.35 | 0.21 | 0.83 | 0.28 | 0.17 |   |   |   |  | Vz | H= | 3.2 |   |   |   | 0.52 | 0.3 | 0.21 | 0.39 | 0.22 | 0.16 | 0.31 | 0.18 | 0.13 |   |   |   |  |   | H= | 3.8 |   |   |   | 0.3 | 0.21 | 0.16 | 0.22 | 0.16 | 0.12 | 0.18 | 0.13 | 0.1 |   |   |   |  | Vk |   | 4.6 | 2.6 | 1.6 |   |  | X0,25 |   | 2.9 | 2.5 | 2.2 |   |  | Ps |   | 15 | 5 | 2 |   |  | Lw(A) |   | 39 | 28 | <20 |   |  | 600 |   | H= | 2.7 |   |   |   |   |   |   | 1.56 | 0.52 | 0.31 | 1.25 | 0.42 | 0.25 | 1.04 | 0.35 | 0.21 |  | Vz | H= | 3.2 |   |   |   |   |   |   | 0.59 | 0.34 | 0.23 | 0.47 | 0.27 | 0.19 | 0.39 | 0.22 | 0.16 |  |   | H= | 3.8 |   |   |   |   |   |   | 0.34 | 0.23 | 0.18 | 0.27 | 0.19 | 0.14 | 0.22 | 0.16 | 0.12 |  | Vk |   |   | 3.8 | 2.5 | 1.7 |  | X0,25 |   |   | 3.1 | 2.7 | 2.5 |  | Ps |   |   | 10 | 4 | 2 |  | Lw(A) |   |   | 38 | 29 | 21 |  | 800 |   | H= | 2.7 |   |   |   |   |   |   | 2.09 | 0.7 | 0.42 | 1.67 | 0.56 | 0.33 | 1.39 | 0.46 | 0.28 |  | Vz | H= | 3.2 |   |   |   |   |   |   | 0.78 | 0.45 | 0.31 | 0.63 | 0.36 | 0.25 | 0.52 | 0.3 | 0.21 |  |   | H= | 3.8 |   |   |   |   |   |   | 0.45 | 0.31 | 0.24 | 0.36 | 0.25 | 0.19 | 0.3 | 0.21 | 0.16 |  | Vk |   |   | 5.1 | 3.3 | 2.3 |  | X0,25 |   |   | 3.7 | 3.2 | 2.9 |  | Ps |   |   | 18 | 8 | 4 |  | Lw(A) |   |   | 45 | 36 | 28 |  | 1000 |   | H= | 2.7 |   |   |   |   |   |   |   |   |   | 2.09 | 0.7 | 0.42 | 1.74 | 0.58 | 0.35 |  | Vz | H= | 3.2 |   |   |   |   |   |   |   |   |   | 0.78 | 0.45 | 0.31 | 0.65 | 0.37 | 0.26 |  |   | H= | 3.8 |   |   |   |   |   |   |   |   |   | 0.45 | 0.31 | 0.24 | 0.37 | 0.26 | 0.2 |  | Vk |   |   |   | 4.1 | 2.8 |  | X0,25 |   |   |   | 3.7 | 3.3 |  | Ps |   |   |   | 12 | 5 |  | Lw(A) |   |   |   | 41 | 34 |  | 1200 |   | H= | 2.7 |   |   |   |   |   |   |   |   |   | 2.5 | 0.83 | 0.5 | 2.09 | 0.7 | 0.42 |  | Vz | H= | 3.2 |   |   |   |   |   |   |   |   |   | 0.94 | 0.54 | 0.38 | 0.78 | 0.45 | 0.31 |  |   | H= | 3.8 |   |   |   |   |   |   |   |   |   | 0.54 | 0.38 | 0.29 | 0.45 | 0.31 | 0.24 |  | Vk |   |   |   | 4.9 | 3.4 |  | X0,25 |   |   |   | 4.2 | 3.7 |  | Ps |   |   |   | 17 | 8 |  | Lw(A) |   |   |   | 46 | 38 |  
       
                                          Symbols and specifications
          
        - Q = Air volume in m³/h
 - Ak = Effective surface (free area) in m²
 - B = Distance between the diffusers in m
 - H = Installation height of the diffusers in m
 - Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
 - Vk = Average effective velocity through the diffuser in m/s
 - X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
 - µPs = Static pressure loss given in P
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 -  The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
 - The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
 - In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
 - The pressure losses Ps are given for diffusers without damper of with fully opened damper.
 - The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
         