Air supply ceiling diffusers with adjustable 1- to 4-way pattern perforated plate. 
       
                      
        
 
Explanation
PPTMB = Diffuser type
200 = Diffuser size (connection diameter)
 
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 160  | 300  | 160  |  | 200 | 400  | 200  |  | 250 | 500  | 250  |  
       
                                          Quick selection
    
      |
 | Q | Ak | 0.0302 | 0.0591 | 0.0976 |  |
 | 150 | Vz | H= | 2.7 | 0.97 | 0.32 | 0.19 | 0.69 | 0.23 | 0.14 |   |   |   |  | H= | 3.2 | 0.36 | 0.21 | 0.15 | 0.26 | 0.15 | 0.1 |   |   |   |  | H= | 3.8 | 0.21 | 0.15 | 0.11 | 0.15 | 0.1 | 0.08 |   |   |   |  | Vk | 1.4 | 0.7 |   |  | X0.25 | 2.4 | 2 |   |  | Ps | 8 | 2 |   |  | Lw(A) | 25 | <20 |   |  | 200 | Vz | H= | 2.7 | 1.29 | 0.43 | 0.26 | 0.92 | 0.31 | 0.18 | 0.73 | 0.24 | 0.15 |  | H= | 3.2 | 0.49 | 0.28 | 0.19 | 0.35 | 0.2 | 0.14 | 0.27 | 0.16 | 0.11 |  | H= | 3.8 | 0.28 | 0.19 | 0.15 | 0.2 | 0.14 | 0.11 | 0.16 | 0.11 | 0.08 |  | Vk | 1.8 | 0.9 | 0.6 |  | X0.25 | 2.8 | 2.3 | 2.1 |  | Ps | 13 | 3 | 1 |  | Lw(A) | 34 | <20 | <20 |  | 250 | Vz | H= | 2.7 | 1.62 | 0.54 | 0.32 | 1.15 | 0.38 | 0.23 | 0.91 | 0.3 | 0.18 |  | H= | 3.2 | 0.61 | 0.35 | 0.24 | 0.43 | 0.25 | 0.17 | 0.34 | 0.2 | 0.14 |  | H= | 3.8 | 0.35 | 0.24 | 0.19 | 0.25 | 0.17 | 0.13 | 0.2 | 0.14 | 0.11 |  | Vk | 2.3 | 1.2 | 0.7 |  | X0.25 | 3.1 | 2.6 | 2.3 |  | Ps | 22 | 6 | 2 |  | Lw(A) | 42 | 22 | <20 |  | 300 | Vz | H= | 2.7 |   |   |   | 1.38 | 0.46 | 0.28 | 1.09 | 0.36 | 0.22 |  | H= | 3.2 |   |   |   | 0.52 | 0.3 | 0.21 | 0.41 | 0.23 | 0.16 |  | H= | 3.8 |   |   |   | 0.3 | 0.21 | 0.16 | 0.23 | 0.16 | 0.13 |  | Vk |   | 1.4 | 0.9 |  | X0.25 |   | 2.9 | 2.5 |  | Ps |   | 8 | 3 |  | Lw(A) |   | 28 | <20 |  | 400 | Vz | H= | 2.7 |   |   |   | 1.85 | 0.62 | 0.37 | 1.46 | 0.49 | 0.29 |  | H= | 3.2 |   |   |   | 0.69 | 0.4 | 0.28 | 0.55 | 0.31 | 0.22 |  | H= | 3.8 |   |   |   | 0.4 | 0.28 | 0.21 | 0.31 | 0.22 | 0.17 |  | Vk |   | 1.9 | 1.1 |  | X0.25 |   | 3.4 | 3 |  | Ps |   | 15 | 5 |  | Lw(A) |   | 38 | 23 |  | 600 | Vz | H= | 2.7 |   |   |   |   |   |   | 2.19 | 0.73 | 0.44 |  | H= | 3.2 |   |   |   |   |   |   | 0.82 | 0.47 | 0.33 |  | H= | 3.8 |   |   |   |   |   |   | 0.47 | 0.33 | 0.25 |  | Vk |   |   | 1.7 |  | X0.25 |   |   | 3.8 |  | Ps |   |   | 12 |  | Lw(A) |   |   | 36 |  | 800 | Vz | H= | 2.7 |   |   |   |   |   |   | 2.92 | 0.97 | 0.58 |  | H= | 3.2 |   |   |   |   |   |   | 1.09 | 0.63 | 0.44 |  | H= | 3.8 |   |   |   |   |   |   | 0.63 | 0.44 | 0.34 |  | Vk |   |   | 2.3 |  | X0.25 |   |   | 4.7 |  | Ps |   |   | 22 |  | Lw(A) |   |   | 46 |  
       
                                          Symbols and specifications
          
        - Q = Air Volume in m³/h
 - Ak = Effective surface (free area) in m²
 - B = Distance between diffusers in m
 - H = Installation height of the diffusers in m
 - Vz = Maximum velocity at the occupied zone regarding distance between diffusers and installation height in m/s
 - Vk = Average effective velocity through the grill in m/s
 - X0.25 = Throw length in m at an endvelocity Vt of 0,25m/s
 - Ps = Static pressure loss given in Pa
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 - The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
 - The table values are given for the adjustable deflection plates set at its standard position to achieve an air flow pattern in 4 direction 
 - The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
 - In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
 - The pressure losses Ps are given for grilles without damper of with fully opened damper.
 - The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
 
         
                                                  Placement instruction
    
                       |