Round ceiling diffusers with adjustable cones 
       
                      
      
        | Dimensions
      |
 | 160 
 | 158 | 595x595 | 310 | 105 |  | 200 | 198 | 595x595 | 395 | 118 |  | 250 | 248 | 595x595 | 490 | 135 |  | 315 | 313 | 595x595 | 615 | 145 | 
 Quick selection
      |
 | Q | Ak summer | 0.031 | 0.046 | 0.069 | 0.106 |  | Ak winter | 0.029 | 0.042 | 0.06 | 0.088 |  |
 | 200 |  | H= | 2.7 | 0.43 | 0.31 | 0.24 | 0.33 | 0.24 | 0.18 |  |  |  |  |  |  |  | Vz | H= | 3.2 | 0.32 | 0.25 | 0.2 | 0.25 | 0.19 | 0.15 |  |  |  |  |  |  |  |  | H= | 3.8 | 0.25 | 0.2 | 0.17 | 0.19 | 0.15 | 0.13 |  |  |  |  |  |  |  | Vk summer | 1.8 | 1.2 |  |  |  | Vk winter | 1.9 | 1.3 |  |  |  | X0,25 | 2.6 | 2 |  |  |  | Y0,25 @Dt +10K | 2.3 | 1.4 |  |  |  | Ps summer | 5 | 2 |  |  |  | Ps winter | 16 | 7 |  |  |  | Lw(A) summer | <20 | <20 |  |  |  | Lw(A) winter | 30 | <20 |  |  |  | 300 |  | H= | 2.7 | 0.64 | 0.46 | 0.36 | 0.49 | 0.35 | 0.27 | 0.26 | 0.2 | 0.18 |  |  |  |  | Vz | H= | 3.2 | 0.48 | 0.37 | 0.3 | 0.37 | 0.28 | 0.23 | 0.21 | 0.17 | 0.16 |  |  |  |  |  | H= | 3.8 | 0.37 | 0.3 | 0.25 | 0.28 | 0.23 | 0.19 | 0.17 | 0.15 | 0.13 |  |  |  |  | Vk summer | 2.7 | 1.8 | 1.2 |  |  | Vk winter | 2.9 | 2 | 1.4 |  |  | X0,25 | 3.9 | 3 | 2.2 |  |  | Y0,25 @Dt +10K | 3.2 | 2.8 | 2 |  |  | Ps summer | 12 | 5 | 2 |  |  | Ps winter | 36 | 16 | 8 |  |  | Lw(A) summer | 27 | <20 | <20 |  |  | Lw(A) winter | 44 | 33 | 21 |  |  | 400 |  | H= | 2.7 | 0.86 | 0.61 | 0.48 | 0.66 | 0.47 | 0.37 | 0.35 | 0.27 | 0.25 | 0.18 | 0.17 | 0.15 |  | Vz | H= | 3.2 | 0.64 | 0.5 | 0.4 | 0.49 | 0.38 | 0.31 | 0.28 | 0.23 | 0.21 | 0.15 | 0.14 | 0.13 |  |  | H= | 3.8 | 0.5 | 0.4 | 0.34 | 0.38 | 0.31 | 0.26 | 0.23 | 0.19 | 0.18 | 0.13 | 0.12 | 0.11 |  | Vk summer | 3.6 | 2.4 | 1.6 | 1 |  | Vk winter | 3.8 | 2.6 | 1.9 | 1.3 |  | X0,25 | 5.2 | 3.9 | 3 | 2 |  | Y0,25 @Dt +10K | 4.2 | 3.4 | 3.2 | 2.6 |  | Ps summer | 21 | 8 | 3 | 1 |  | Ps winter | 62 | 27 | 14 | 6 |  | Lw(A) summer | 37 | 26 | <20 | <20 |  | Lw(A) winter | 54 | 43 | 31 | <20 |  | 600 |  | H= | 2.7 | 1.29 | 0.92 | 0.72 | 0.99 | 0.71 | 0.55 | 0.53 | 0.41 | 0.37 | 0.29 | 0.26 | 0.24 |  | Vz | H= | 3.2 | 0.97 | 0.74 | 0.6 | 0.74 | 0.57 | 0.46 | 0.43 | 0.35 | 0.32 | 0.25 | 0.23 | 0.21 |  |  | H= | 3.8 | 0.74 | 0.6 | 0.51 | 0.57 | 0.46 | 0.39 | 0.35 | 0.29 | 0.27 | 0.21 | 0.19 | 0.18 |  | Vk summer | 5.4 | 3.6 | 2.4 | 1.6 |  | Vk winter | 5.7 | 4 | 2.8 | 1.9 |  | X0,25 | 7.7 | 5.9 | 4.4 | 3.2 |  | Y0,25 @Dt +10K | 6 | 4.7 | 4.1 | 3.8 |  | Ps summer | 47 | 18 | 7 | 3 |  | Ps winter | 137 | 63 | 29 | 13 |  | Lw(A) summer | 52 | 40 | 27 | <20 |  | Lw(A) winter | 68 | 57 | 45 | 32 |  | 800 |  | H= | 2.7 |  |  |  | 1.32 | 0.94 | 0.73 | 0.7 | 0.55 | 0.49 | 0.39 | 0.35 | 0.32 |  | Vz | H= | 3.2 |  |  |  | 0.99 | 0.76 | 0.62 | 0.57 | 0.46 | 0.42 | 0.32 | 0.3 | 0.27 |  |  | H= | 3.8 |  |  |  | 0.76 | 0.62 | 0.52 | 0.46 | 0.39 | 0.36 | 0.27 | 0.25 | 0.24 |  | Vk summer |  | 4.8 | 3.2 | 2.1 |  | Vk winter |  | 5.3 | 3.7 | 2.5 |  | X0,25 |  | 7.9 | 5.9 | 4.2 |  | Y0,25 @Dt +10K |  | 6.1 | 5 | 4.5 |  | Ps summer |  | 32 | 12 | 5 |  | Ps winter |  | 110 | 51 | 22 |  | Lw(A) summer |  | 50 | 37 | 23 |  | Lw(A) winter |  | 67 | 55 | 42 | 
 Symbols and specifications
        Q = Air Volume in m³/hAk winter = Effective surface (free area) in m² given at the upper position of the inner adjustable coneAk summer = Effective surface (free area) in m² given at the lower position of the inner adjustable coneB = Distance between diffusers in mH = Installation height of the diffusers in mVz = Maximum velocity at the occupied zone, given for cooling at the lower position of the inner adjustable cone, regarding the distance between diffusers and installation height in m/sVk winter = Average effective velocity for Ak winter through the diffuser in m/sVk summer = Average effective velocity for Ak summer through the diffuser in m/sX0.25 = Horizontal throw in m at an endvelocity Vt of 0,25m/s isothermal at the lower position of the inner coneY0.25 = Vertical throw in m at an endvelocity Vt of 0,25m/s with a temperature difference of +10K at the upper position of the inner conePs winter = Static pressure loss for Ak winter given in PaPs summer = Static pressure loss for Ak summer given in PaLw(A) winter = Acoustic power for Ak winter in dB(A)Lw(A) summer = Acoustic power for Ak summer in dB(A)
 
 The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.The pressure losses Ps are given for grilles without damper of with fully opened damper.The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.For all special requirements, please contact our engineering office.
 Placement instructionCFD simulation CoolingCFD simulation Heating |