Square swirl ceiling diffusers with adjustable blades
       
                      
        
- Square plenum box, type REV-B
- Square insulated plenum box, type REV-B ISO
- Circular plenum box, type RER-B
- Insulated circular plenum box, type RER-B ISO
- Regulating valve for plenum box, type CRC
 
- Polystyrene plenum box, type PPS-P with duct connection PPS-APD and mounting
bar PPS-MB
(When using PPS-P plenum, a screw of at least 8cm must be provided by the installer himself)      
 
                      
        
- VWR-3A, 600, 24 + REV-B 600 + CRC 250
Explanation
VWR-3A = Diffuser type
600 = Plate size
24 = Slot quantity 
 
Accessories
REV-B 600 = Plenum box for diffuser with 24 slots
CRC = Regulating valve for plenum box
250 = Plenum box connection diameter 250
       
              
      
      
        | Dimensions
      |
 | 400/16 
 | 16 
 | 395x395 
 |  | 500/16 | 16 
 | 495x495 
 |  | 600/16 | 16 
 | 595x595 
 |  | 600/24 | 24 
 | 595x595 
 |  | 625/24 | 24 
 | 623x623 
 | 
 Flow patterns deflectorsQuick selection
      |
 | Q | Ak | 0.01548 | 0.03718 |  |
 | 150 |  | H= | 2.7 | 0.09 | 0.12 | 0.08 |  |  |  |  | Vz | H= | 3.2 | 0.06 | 0.07 | 0.05 |  |  |  |  |  | H= | 3.8 | 0.04 | 0.05 | 0.04 |  |  |  |  | Vk | 2.7 |  |  | X0,25 | 1.1 |  |  | Ps | 4 |  |  | Lw(A) | <20 |  |  | 200 |  | H= | 2.7 | 0.12 | 0.15 | 0.11 | 0.09 | 0.11 | 0.09 |  | Vz | H= | 3.2 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.05 |  |  | H= | 3.8 | 0.05 | 0.07 | 0.05 | 0.04 | 0.05 | 0.04 |  | Vk | 3.6 | 1.5 |  | X0,25 | 1.5 | 0.9 |  | Ps | 8 | 2 |  | Lw(A) | 22 | <20 |  | 250 |  | H= | 2.7 | 0.15 | 0.19 | 0.13 | 0.11 | 0.14 | 0.11 |  | Vz | H= | 3.2 | 0.1 | 0.12 | 0.08 | 0.07 | 0.09 | 0.07 |  |  | H= | 3.8 | 0.07 | 0.08 | 0.06 | 0.05 | 0.06 | 0.05 |  | Vk | 4.5 | 1.9 |  | X0,25 | 1.8 | 1.2 |  | Ps | 12 | 4 |  | Lw(A) | 29 | <20 |  | 300 |  | H= | 2.7 | 0.18 | 0.23 | 0.16 | 0.13 | 0.17 | 0.13 |  | Vz | H= | 3.2 | 0.12 | 0.15 | 0.1 | 0.08 | 0.1 | 0.08 |  |  | H= | 3.8 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.06 |  | Vk | 5.4 | 2.2 |  | X0,25 | 2.2 | 1.4 |  | Ps | 18 | 5 |  | Lw(A) | 35 | <20 |  | 350 |  | H= | 2.7 |  |  |  | 0.16 | 0.19 | 0.15 |  | Vz | H= | 3.2 |  |  |  | 0.1 | 0.12 | 0.09 |  |  | H= | 3.8 |  |  |  | 0.07 | 0.08 | 0.07 |  | Vk |  | 2.6 |  | X0,25 |  | 1.7 |  | Ps |  | 7 |  | Lw(A) |  | <20 |  | 400 |  | H= | 2.7 |  |  |  | 0.18 | 0.22 | 0.17 |  | Vz | H= | 3.2 |  |  |  | 0.11 | 0.14 | 0.11 |  |  | H= | 3.8 |  |  |  | 0.08 | 0.1 | 0.08 |  | Vk |  | 3 |  | X0,25 |  | 1.9 |  | Ps |  | 9 |  | Lw(A) |  | 24 |  | 500 |  | H= | 2.7 |  |  |  | 0.22 | 0.28 | 0.21 |  | Vz | H= | 3.2 |  |  |  | 0.14 | 0.17 | 0.14 |  |  | H= | 3.8 |  |  |  | 0.1 | 0.12 | 0.09 |  | Vk |  | 3.7 |  | X0,25 |  | 2.4 |  | Ps |  | 14 |  | Lw(A) |  | 30 |  | 600 |  | H= | 2.7 |  |  |  | 0.27 | 0.33 | 0.26 |  | Vz | H= | 3.2 |  |  |  | 0.17 | 0.21 | 0.16 |  |  | H= | 3.8 |  |  |  | 0.12 | 0.15 | 0.11 |  | Vk |  | 4.5 |  | X0,25 |  | 2.8 |  | Ps |  | 20 |  | Lw(A) |  | 36 | 
 Symbols and specifications
        Q = Air volume in m³/hAk = Effective surface (free area) in m²B = Distance between the diffusers in mH = Installation height of the diffusers in mVz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/sVk = Average effective velocity through the diffuser in m/sX0.25 = Throw length in m at an end velocity Vt of 0,25m/sPs = Static pressure loss given in PaLw(A) = Acoustic power in dB(A)
 
 The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.The pressure losses Ps are given for diffusers without damper of with fully opened damper.The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.For all special requirements, please contact our engineering office.
 Placement instruction |