Square swirl ceiling diffusers with adjustable blades
       
                      
        
- Square plenum box, type REV-B
 
- Square insulated plenum box, type REV-B ISO
 
- Circular plenum box, type RER-B
 
- Insulated circular plenum box, type RER-B ISO
 
- Regulating valve for plenum box, type CRC
 - Polystyrene plenum box, type PPS-P with duct connection PPS-APD and mounting
bar PPS-MB
 
(When using PPS-P plenum, a screw of at least 8cm must be provided by the installer himself)      
 
                      
        
- VWR-3A, 600, 24 + REV-B 600 + CRC 250
 
Explanation
VWR-3A = Diffuser type
600 = Plate size
24 = Slot quantity 
 
Accessories
REV-B 600 = Plenum box for diffuser with 24 slots
CRC = Regulating valve for plenum box
250 = Plenum box connection diameter 250
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 400/16 
 | 16 
 | 395x395 
 |  | 500/16 | 16 
 | 495x495 
 |  | 600/16 | 16 
 | 595x595 
 |  | 600/24 | 24 
 | 595x595 
 |  | 625/24 | 24 
 | 623x623 
 |  
       
                                              Flow patterns deflectors
    
                                          Quick selection
    
      |
 | Q | Ak | 0.01548 | 0.03718 |  |
 | 150 |   | H= | 2.7 | 0.09 | 0.12 | 0.08 |   |   |   |  | Vz | H= | 3.2 | 0.06 | 0.07 | 0.05 |   |   |   |  |   | H= | 3.8 | 0.04 | 0.05 | 0.04 |   |   |   |  | Vk | 2.7 |   |  | X0,25 | 1.1 |   |  | Ps | 4 |   |  | Lw(A) | <20 |   |  | 200 |   | H= | 2.7 | 0.12 | 0.15 | 0.11 | 0.09 | 0.11 | 0.09 |  | Vz | H= | 3.2 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.05 |  |   | H= | 3.8 | 0.05 | 0.07 | 0.05 | 0.04 | 0.05 | 0.04 |  | Vk | 3.6 | 1.5 |  | X0,25 | 1.5 | 0.9 |  | Ps | 8 | 2 |  | Lw(A) | 22 | <20 |  | 250 |   | H= | 2.7 | 0.15 | 0.19 | 0.13 | 0.11 | 0.14 | 0.11 |  | Vz | H= | 3.2 | 0.1 | 0.12 | 0.08 | 0.07 | 0.09 | 0.07 |  |   | H= | 3.8 | 0.07 | 0.08 | 0.06 | 0.05 | 0.06 | 0.05 |  | Vk | 4.5 | 1.9 |  | X0,25 | 1.8 | 1.2 |  | Ps | 12 | 4 |  | Lw(A) | 29 | <20 |  | 300 |   | H= | 2.7 | 0.18 | 0.23 | 0.16 | 0.13 | 0.17 | 0.13 |  | Vz | H= | 3.2 | 0.12 | 0.15 | 0.1 | 0.08 | 0.1 | 0.08 |  |   | H= | 3.8 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.06 |  | Vk | 5.4 | 2.2 |  | X0,25 | 2.2 | 1.4 |  | Ps | 18 | 5 |  | Lw(A) | 35 | <20 |  | 350 |   | H= | 2.7 |   |   |   | 0.16 | 0.19 | 0.15 |  | Vz | H= | 3.2 |   |   |   | 0.1 | 0.12 | 0.09 |  |   | H= | 3.8 |   |   |   | 0.07 | 0.08 | 0.07 |  | Vk |   | 2.6 |  | X0,25 |   | 1.7 |  | Ps |   | 7 |  | Lw(A) |   | <20 |  | 400 |   | H= | 2.7 |   |   |   | 0.18 | 0.22 | 0.17 |  | Vz | H= | 3.2 |   |   |   | 0.11 | 0.14 | 0.11 |  |   | H= | 3.8 |   |   |   | 0.08 | 0.1 | 0.08 |  | Vk |   | 3 |  | X0,25 |   | 1.9 |  | Ps |   | 9 |  | Lw(A) |   | 24 |  | 500 |   | H= | 2.7 |   |   |   | 0.22 | 0.28 | 0.21 |  | Vz | H= | 3.2 |   |   |   | 0.14 | 0.17 | 0.14 |  |   | H= | 3.8 |   |   |   | 0.1 | 0.12 | 0.09 |  | Vk |   | 3.7 |  | X0,25 |   | 2.4 |  | Ps |   | 14 |  | Lw(A) |   | 30 |  | 600 |   | H= | 2.7 |   |   |   | 0.27 | 0.33 | 0.26 |  | Vz | H= | 3.2 |   |   |   | 0.17 | 0.21 | 0.16 |  |   | H= | 3.8 |   |   |   | 0.12 | 0.15 | 0.11 |  | Vk |   | 4.5 |  | X0,25 |   | 2.8 |  | Ps |   | 20 |  | Lw(A) |   | 36 |  
       
                                          Symbols and specifications
          
        - Q = Air volume in m³/h
 - Ak = Effective surface (free area) in m²
 - B = Distance between the diffusers in m
 - H = Installation height of the diffusers in m
 - Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
 - Vk = Average effective velocity through the diffuser in m/s
 - X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
 - Ps = Static pressure loss given in Pa
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 - The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
 - The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
 - In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
 - The pressure losses Ps are given for diffusers without damper of with fully opened damper.
 - The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
          
                                                  Placement instruction
    
                       |