Circular adjustable swirl ceiling diffuser for high ceiling
       
                      
        
Explanation
PS/RWR-4 = Diffuser type
315 = Neck size of diffuser 
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 | PS/RWR-4 200 | 198 | 248 | 96 | 180 | 20 | 40 | 30 |  | PS/RWR-4 250 | 248 | 298 | 133 | 205 | 30 | 40 | 30 |  | PS/RWR-4 315 | 313 | 398 | 175 | 230 | 30 | 40 | 30 |  
       
                                          Quick selection
    
      |
 | Q | Ak | 0.0305 | 0.0479 | 0.0765 |  |
 | 300 | B(min) | 2.4 | 1.6 |   |  | Vk | 2.7 | 1.7 |   |  | Ps | 13 | 5 |   |  | Lw(A) | 35 | 24 |   |  | 400 | B(min) | 3 | 2.2 | 2 |  | Vk | 3.6 | 2.3 | 1.5 |  | Ps | 22 | 9 | 4 |  | Lw(A) | 44 | 32 | 22 |  | 500 | B(min) | 3.8 | 2.8 | 2 |  | Vk | 4.6 | 2.9 | 1.8 |  | Ps | 34 | 13 | 5 |  | Lw(A) | 51 | 39 | 24 |  | 600 | B(min) |   | 3.4 | 2.4 |  | Vk |   | 3.5 | 2.2 |  | Ps |   | 20 | 7 |  | Lw(A) |   | 44 | 29 |  | 800 | B(min) |   |   | 3 |  | Vk |   |   | 2.9 |  | Ps |   |   | 14 |  | Lw(A) |   |   | 38 |  | 1000 | B(min) |   |   | 3.8 |  | Vk |   |   | 3.6 |  | Ps |   |   | 22 |  | Lw(A) |   |   | 45 |  
       
                                          Symbols and specifications
          
        - Q = Air Volume in m³/h
 - Ak = Effective surface (free area) of the neck of the diffuser in m²
 - Hm = Advised minimum - maximum mounting height in m
 - Bmin = Advised minimum distance between diffusers in m
 - Vk = Air velocity trough the neck of the diffuser in m/s
 - Ps = Static pressure loss in Pa
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 - The values are given for isothermal supply air without Coanda effect.
 - The values in the table are given at an inclination angle α of the vanes of the diffuser set at 45°.
 - In order to achieve a high comfort level, the angle of the blades can be set according to the temperature difference Δt between the supply air and room air temperature. (see selection graphs)
 - Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
          
                                                  Placement instruction
    
                                              Noise selection table
    
                                              Placement height selector
    
                                              Minimum distance selection 
    
                                              Angle setting size 200
    
                                              Angle setting size 250
    
                                              Angle setting size 315
    
                       |