Linear slot diffusers with adjustable drum deflector
       
                      
        
- ASR-2 RAL9016, 1500 + PR-ASR 2 1500 + ASR-CON
 
 
Explanation 
ASR RAL9016 = Diffuser type in white finish
2 = Slot quantity
1500 = Length of diffuser
 
Accessories (optional)
PR-ASR 2 1500 = Not-insulated plenum box for diffuser of 2 slots with a length of 1500mm
ASR-CON = Connection piece to mount several diffusers in line
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 | ASR 1 | 800 | 1 x 100 | 39 | 56 |  | 1000 | 1 x 100 |  | 1500 | 2 x 100 |  | 2000 | 3 x 100 |  | ASR 2 | 800 | 1 x 150 | 77 | 94 |  | 1000 | 2 x 150 |  | 1500 | 3 x 150 |  | 2000 | 4 x 150 |  | ASR 3 | 800 | 1 x 200 | 115 | 132 |  | 1000 | 2 x 200 |  | 1500 | 3 x 200 |  | 2000 | 4 x 200 |  | ASR 4 | 800 | 2 x 200 | 153 | 170 |  | 1000 | 2 x 200 |  | 1500 | 3 x 200 |  | 2000 | 4 x 200 |  
       
                                          Quick selection
    
      |
 | Q | Ak | 0.00496 | 0.0062 | 0.0093 | 0.00992 | 0.0124 | 0.01488 | 0.0186 | 0.01984 | 0.0248 | 0.0279 | 0.0372 | 0.0496 |  | 50 | Vk | 2.8 | 2.2 | 1.5 |   |   |   |   |   |   |   |   |   |  | X0,25 | 3.2 | 2.8 | 2.2 |   |   |   |   |   |   |   |   |   |  | Ps | 9 | 6 | 3 |   |   |   |   |   |   |   |   |   |  | Lw(A) | <20 | <20 | <20 |   |   |   |   |   |   |   |   |   |  | 100 | Vk |   | 4.5 | 3 | 2.8 | 2.2 | 1.9 | 1.5 |   |   |   |   |   |  | X0,25 |   | 5.5 | 4.3 | 4.2 | 3.6 | 3.2 | 2.8 |   |   |   |   |   |  | Ps |   | 24 | 12 | 11 | 7 | 5 | 4 |   |   |   |   |   |  | Lw(A) |   | 33 | 24 | 23 | <20 | <20 | <20 |   |   |   |   |   |  | 150 | Vk |   |   | 4.5 | 4.2 | 3.4 | 2.8 | 2.2 | 2.1 | 1.7 | 1.5 |   |   |  | X0,25 |   |   | 6.5 | 6.2 | 5.4 | 4.9 | 4.2 | 4.1 | 3.5 | 3.3 |   |   |  | Ps |   |   | 27 | 24 | 17 | 12 | 8 | 7 | 5 | 4 |   |   |  | Lw(A) |   |   | 35 | 34 | 30 | 26 | 21 | <20 | <20 | <20 |   |   |  | 200 | Vk |   |   |   |   | 4.5 | 3.7 | 3 | 2.8 | 2.2 | 2 | 1.5 |   |  | X0,25 |   |   |   |   | 7.2 | 6.5 | 5.6 | 5.4 | 4.7 | 4.4 | 3.7 |   |  | Ps |   |   |   |   | 30 | 22 | 15 | 13 | 9 | 7 | 4 |   |  | Lw(A) |   |   |   |   | 37 | 34 | 29 | 28 | 23 | 20 | <20 |   |  | 250 | Vk |   |   |   |   |   | 4.7 | 3.7 | 3.5 | 2.8 | 2.5 | 1.9 |   |  | X0,25 |   |   |   |   |   | 8.1 | 7 | 6.8 | 5.9 | 5.5 | 4.6 |   |  | Ps |   |   |   |   |   | 34 | 23 | 21 | 14 | 11 | 7 |   |  | Lw(A) |   |   |   |   |   | 40 | 35 | 34 | 29 | 27 | 21 |   |  | 300 | Vk |   |   |   |   |   |   | 4.5 | 4.2 | 3.4 | 3 | 2.2 | 1.7 |  | X0,25 |   |   |   |   |   |   | 8.5 | 8.1 | 7.1 | 6.6 | 5.5 | 4.6 |  | Ps |   |   |   |   |   |   | 33 | 30 | 20 | 16 | 10 | 6 |  | Lw(A) |   |   |   |   |   |   | 40 | 39 | 34 | 31 | 26 | <20 |  | 350 | Vk |   |   |   |   |   |   |   | 4.9 | 3.9 | 3.5 | 2.6 | 2 |  | X0,25 |   |   |   |   |   |   |   | 9.5 | 8.3 | 7.7 | 6.4 | 5.4 |  | Ps |   |   |   |   |   |   |   | 40 | 27 | 22 | 14 | 8 |  | Lw(A) |   |   |   |   |   |   |   | 43 | 38 | 36 | 30 | 24 |  | 400 | Vk |   |   |   |   |   |   |   |   | 4.5 | 4 | 3 | 2.2 |  | X0,25 |   |   |   |   |   |   |   |   | 9.4 | 8.8 | 7.4 | 6.2 |  | Ps |   |   |   |   |   |   |   |   | 36 | 29 | 18 | 11 |  | Lw(A) |   |   |   |   |   |   |   |   | 42 | 39 | 33 | 27 |  | 500 | Vk |   |   |   |   |   |   |   |   |   | 5 | 3.7 | 2.8 |  | X0,25 |   |   |   |   |   |   |   |   |   | 11 | 9.2 | 7.7 |  | Ps |   |   |   |   |   |   |   |   |   | 46 | 28 | 17 |  | Lw(A) |   |   |   |   |   |   |   |   |   | 45 | 39 | 33 |  | 600 | Vk |   |   |   |   |   |   |   |   |   |   | 4.5 | 3.4 |  | X0,25 |   |   |   |   |   |   |   |   |   |   | 11 | 9.2 |  | Ps |   |   |   |   |   |   |   |   |   |   | 40 | 24 |  | Lw(A) |   |   |   |   |   |   |   |   |   |   | 44 | 38 |  
       
                                          Symbols and specifications
          
        - Q = Air Volume in m³/h
 - Ak = Effective surface (free area) in m²
 - Vk = Average effective velocity through the grill in m/s
 - X0.25 = Throw length in m at an endvelocity Vt of 0,25m/s
 - Ps = Static pressure loss given in Pa
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 - The horizontal throw X0.25 is given at an end velocity of 0.25m/s with all deflectors positioned for a maximal horizontal one-way throw installed in smooth ceiling without any obstacles.
 
 - The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
 - The pressure losses Ps are given for grilles without damper.
 - The acoustic power Lw(A) are given for grilles without damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
         
                                                  Placement instruction
    
                       |