Multinozzle ceiling diffusers with high induction rate, consisting of a square plate with individual adjustable nozzles arranged in a circular pattern and to be equipped with galvanized steel plenumbox (PS/SNC-1A = SNC-1A diffuser in plate 596 x 596)
       
                      
        
- SNC-1A, 600 + RER-B 600 + CRC 250
 
Explanation
SNC-1A = Diffuser type
600 = Diffuser size
Accessories 
RER-B = Circular plenum box
600 = Size plenum box
CRC = Regulating valve for plenum box
250 = Plenum box connection diameter 250
       
              
      
      
        
                                    
                                    
                                                      
    
                                          Dimensions
    
      |
 SNC-1A 300  | 296x296  | 22 |  SNC-1A 400  | 396x396  | 42 |  SNC-1A 500  | 496x496  | 68 |  SNC-1A 600  | 596x596  | 100 |  SNC-1A 625*  | 621x621  | 100 |  PS/SNC-1A 300/596  | 596x596  | 22 |  PS/SNC-1A 400/596  | 596x596  | 42 |  PS/SNC-1A 500/596  | 596x596  | 68 |  | * niet meer verkrijgbaar / n'est plus disponible / no longer available |  
       
                                          Quick selection
    
      |
 | Q | Ak | 0.0057 | 0.0114 | 0.0153 | 0.0258 |  |
 | 50 |   | H= | 2.7 | 0.3 | 0.12 | 0.06 | 0.25 | 0.1 | 0.05 |   |   |   |   |   |   |  | Vz | H= | 3.2 | 0.14 | 0.07 | 0.04 | 0.12 | 0.06 | 0.03 |   |   |   |   |   |   |  |   | H= | 3.8 | 0.07 | 0.04 | 0.02 | 0.06 | 0.03 | 0.02 |   |   |   |   |   |   |  | Vk | 2.4 | 1.2 |   |   |  | X0,25 | 1.6 | 1.5 |   |   |  | Ps | 6 | 2 |   |   |  | Lw(A) | 24 | <20 |   |   |  | 75 |   | H= | 2.7 | 0.42 | 0.19 | 0.11 | 0.34 | 0.15 | 0.08 | 0.32 | 0.14 | 0.08 |   |   |   |  | Vz | H= | 3.2 | 0.22 | 0.12 | 0.07 | 0.17 | 0.09 | 0.06 | 0.16 | 0.08 | 0.05 |   |   |   |  |   | H= | 3.8 | 0.12 | 0.07 | 0.05 | 0.09 | 0.06 | 0.04 | 0.08 | 0.05 | 0.03 |   |   |   |  | Vk | 3.7 | 1.8 | 1.4 |   |  | X0,25 | 1.8 | 1.7 | 1.6 |   |  | Ps | 13 | 4 | 2 |   |  | Lw(A) | 33 | <20 | <20 |   |  | 100 |   | H= | 2.7 | 0.53 | 0.27 | 0.16 | 0.42 | 0.2 | 0.12 | 0.38 | 0.18 | 0.1 | 0.3 | 0.13 | 0.07 |  | Vz | H= | 3.2 | 0.29 | 0.17 | 0.11 | 0.22 | 0.13 | 0.08 | 0.2 | 0.11 | 0.07 | 0.15 | 0.08 | 0.05 |  |   | H= | 3.8 | 0.17 | 0.11 | 0.08 | 0.13 | 0.08 | 0.05 | 0.11 | 0.07 | 0.05 | 0.08 | 0.05 | 0.03 |  | Vk | 4.9 | 2.4 | 1.8 | 1.1 |  | X0,25 | 2.1 | 1.9 | 1.8 | 1.6 |  | Ps | 24 | 7 | 4 | 2 |  | Lw(A) | 38 | 23 | <20 | <20 |  | 150 |   | H= | 2.7 |   |   |   | 0.58 | 0.3 | 0.19 | 0.51 | 0.26 | 0.16 | 0.39 | 0.18 | 0.11 |  | Vz | H= | 3.2 |   |   |   | 0.33 | 0.2 | 0.14 | 0.29 | 0.17 | 0.11 | 0.21 | 0.12 | 0.07 |  |   | H= | 3.8 |   |   |   | 0.2 | 0.14 | 0.1 | 0.17 | 0.11 | 0.08 | 0.12 | 0.07 | 0.05 |  | Vk |   | 3.7 | 2.7 | 1.6 |  | X0,25 |   | 2.3 | 2.1 | 1.8 |  | Ps |   | 16 | 9 | 3 |  | Lw(A) |   | 33 | 27 | <20 |  | 200 |   | H= | 2.7 |   |   |   | 0.71 | 0.4 | 0.26 | 0.63 | 0.34 | 0.22 | 0.49 | 0.25 | 0.15 |  | Vz | H= | 3.2 |   |   |   | 0.43 | 0.28 | 0.19 | 0.37 | 0.23 | 0.16 | 0.27 | 0.16 | 0.11 |  |   | H= | 3.8 |   |   |   | 0.28 | 0.19 | 0.14 | 0.23 | 0.16 | 0.12 | 0.16 | 0.11 | 0.08 |  | Vk |   | 4.9 | 3.6 | 2.2 |  | X0,25 |   | 2.7 | 2.4 | 2 |  | Ps |   | 28 | 16 | 6 |  | Lw(A) |   | 40 | 34 | 23 |  | 250 |   | H= | 2.7 |   |   |   |   |   |   | 0.74 | 0.42 | 0.28 | 0.57 | 0.3 | 0.19 |  | Vz | H= | 3.2 |   |   |   |   |   |   | 0.46 | 0.3 | 0.21 | 0.33 | 0.2 | 0.14 |  |   | H= | 3.8 |   |   |   |   |   |   | 0.3 | 0.21 | 0.16 | 0.2 | 0.14 | 0.1 |  | Vk |   |   | 4.5 | 2.7 |  | X0,25 |   |   | 2.8 | 2.3 |  | Ps |   |   | 25 | 9 |  | Lw(A) |   |   | 40 | 28 |  | 300 |   | H= | 2.7 |   |   |   |   |   |   | 0.85 | 0.5 | 0.34 | 0.64 | 0.35 | 0.23 |  | Vz | H= | 3.2 |   |   |   |   |   |   | 0.54 | 0.36 | 0.26 | 0.39 | 0.24 | 0.17 |  |   | H= | 3.8 |   |   |   |   |   |   | 0.36 | 0.26 | 0.2 | 0.24 | 0.17 | 0.12 |  | Vk |   |   | 5.4 | 3.2 |  | X0,25 |   |   | 3.2 | 2.5 |  | Ps |   |   | 35 | 13 |  | Lw(A) |   |   | 45 | 33 |  | 350 |   | H= | 2.7 |   |   |   |   |   |   |   |   |   | 0.73 | 0.42 | 0.27 |  | Vz | H= | 3.2 |   |   |   |   |   |   |   |   |   | 0.45 | 0.29 | 0.21 |  |   | H= | 3.8 |   |   |   |   |   |   |   |   |   | 0.29 | 0.21 | 0.16 |  | Vk |   |   |   | 3.8 |  | X0,25 |   |   |   | 2.8 |  | Ps |   |   |   | 18 |  | Lw(A) |   |   |   | 37 |  | 400 |   | H= | 2.7 |   |   |   |   |   |   |   |   |   | 0.79 | 0.47 | 0.31 |  | Vz | H= | 3.2 |   |   |   |   |   |   |   |   |   | 0.51 | 0.33 | 0.24 |  |   | H= | 3.8 |   |   |   |   |   |   |   |   |   | 0.33 | 0.24 | 0.18 |  | Vk |   |   |   | 4.3 |  | X0,25 |   |   |   | 3 |  | Ps |   |   |   | 23 |  | Lw(A) |   |   |   | 41 |  | 450 |   | H= | 2.7 |   |   |   |   |   |   |   |   |   | 0.86 | 0.52 | 0.36 |  | Vz | H= | 3.2 |   |   |   |   |   |   |   |   |   | 0.56 | 0.38 | 0.28 |  |   | H= | 3.8 |   |   |   |   |   |   |   |   |   | 0.38 | 0.28 | 0.21 |  | Vk |   |   |   | 4.8 |  | X0,25 |   |   |   | 3.3 |  | Ps |   |   |   | 29 |  | Lw(A) |   |   |   | 44 |  
       
                                          Symbols and specifications
          
        - Q = Air volume in m³/h
 - Ak = Effective surface (free area) in m²
 - B = Distance between the diffusers in m
 - H = Installation height of the diffusers in m
 - Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
 - Vk = Average effective velocity through the diffuser in m/s
 - X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
 - Ps = Static pressure loss given in Pa
 - Lw(A) = Acoustic power in dB(A)
 
 
 
 - The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
 - The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
 - In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
 - The pressure losses Ps are given for diffusers without damper of with fully opened damper.
 - The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
 - For all special requirements, please contact our engineering office.
         
                                                  Placement instruction
    
                       |