Swirl ceiling diffusers with high induction rate, consisting of a square plate with multiple fixed curved blades arranged in a circular pattern, to be equipped with galvanized steel plenum box
       
                      
        
- VWR-FCSA, 600 + RER-B 600 + CRC 250
 
Explanation
VWR-FCSA = Diffuser type
600 = Diffuser size/swirl size
 
Accessories
RER-B = Plenum box type
600 = Size plenum box
CRC = Plenum box connection valve
250 = Plenum box connection diameter 250
       
              
      
      
        | Dimensions
      |
 | VWR-FCSA 300 | 238 | 86 | 236 | 296 | 41 | 16 |  | VWR-FCSA 400 | 338 | 140 | 336 | 396 | 41 | 22 |  | VWR-FCSA 500 | 438 | 170 | 436 | 496 | 41 | 24 |  | VWR-FSCA 600 | 538 | 170 | 536 | 596 | 22 | 24 |  | VWR-FSCA 625* | 538 | 170 | 536 | 621 | 22 | 24 |  | * niet meer verkrijgbaar / n'est plus disponible / no longer available | 
 Quick selection
      |
 | Q | Ak | 0.023 | 0.03 | 0.0465 | 0.07 | 0.07 |  |
 | 100 |  | H= | 2.7 | 0.17 | 0.13 | 0.11 |  |  |  |  |  |  |  |  |  |  |  |  |  | Vz | H= | 3.2 | 0.14 | 0.11 | 0.09 |  |  |  |  |  |  |  |  |  |  |  |  |  |  | H= | 3.8 | 0.11 | 0.09 | 0.08 |  |  |  |  |  |  |  |  |  |  |  |  |  | Vk | 1.2 |  |  |  |  |  | X0,25 | 0.9 |  |  |  |  |  | Ps | 7 |  |  |  |  |  | Lw(A) | <20 |  |  |  |  |  | 150 |  | H= | 2.7 | 0.26 | 0.2 | 0.16 | 0.23 | 0.18 | 0.15 |  |  |  |  |  |  |  |  |  |  | Vz | H= | 3.2 | 0.2 | 0.17 | 0.14 | 0.18 | 0.15 | 0.13 |  |  |  |  |  |  |  |  |  |  |  | H= | 3.8 | 0.17 | 0.14 | 0.12 | 0.15 | 0.13 | 0.12 |  |  |  |  |  |  |  |  |  |  | Vk | 1.8 | 1.4 |  |  |  |  | X0,25 | 1.6 | 1.3 |  |  |  |  | Ps | 17 | 5 |  |  |  |  | Lw(A) | 26 | <20 |  |  |  |  | 200 |  | H= | 2.7 | 0.34 | 0.26 | 0.21 | 0.29 | 0.23 | 0.2 | 0.21 | 0.17 | 0.14 |  |  |  |  |  |  |  | Vz | H= | 3.2 | 0.27 | 0.22 | 0.19 | 0.24 | 0.2 | 0.17 | 0.17 | 0.15 | 0.13 |  |  |  |  |  |  |  |  | H= | 3.8 | 0.22 | 0.19 | 0.16 | 0.2 | 0.17 | 0.15 | 0.15 | 0.13 | 0.12 |  |  |  |  |  |  |  | Vk | 2.4 | 1.9 | 1.2 |  |  |  | X0,25 | 2.2 | 1.9 | 1.1 |  |  |  | Ps | 30 | 8 | 2 |  |  |  | Lw(A) | 34 | <20 | <20 |  |  |  | 250 |  | H= | 2.7 | 0.43 | 0.33 | 0.27 | 0.36 | 0.29 | 0.24 | 0.25 | 0.2 | 0.17 |  |  |  |  |  |  |  | Vz | H= | 3.2 | 0.34 | 0.28 | 0.23 | 0.3 | 0.25 | 0.21 | 0.21 | 0.18 | 0.16 |  |  |  |  |  |  |  |  | H= | 3.8 | 0.28 | 0.23 | 0.2 | 0.25 | 0.21 | 0.19 | 0.18 | 0.16 | 0.14 |  |  |  |  |  |  |  | Vk | 3 | 2.3 | 1.5 |  |  |  | X0,25 | 2.9 | 2.5 | 1.5 |  |  |  | Ps | 47 | 13 | 3 |  |  |  | Lw(A) | 41 | 24 | <20 |  |  |  | 300 |  | H= | 2.7 | 0.51 | 0.39 | 0.32 | 0.43 | 0.34 | 0.28 | 0.29 | 0.24 | 0.2 | 0.22 | 0.17 | 0.15 | 0.22 | 0.17 | 0.15 |  | Vz | H= | 3.2 | 0.41 | 0.33 | 0.28 | 0.35 | 0.29 | 0.25 | 0.25 | 0.21 | 0.18 | 0.18 | 0.15 | 0.13 | 0.18 | 0.15 | 0.13 |  |  | H= | 3.8 | 0.33 | 0.28 | 0.24 | 0.29 | 0.25 | 0.22 | 0.21 | 0.18 | 0.17 | 0.15 | 0.13 | 0.12 | 0.15 | 0.13 | 0.12 |  | Vk | 3.6 | 2.8 | 1.8 | 1.2 | 1.2 |  | X0,25 | 3.7 | 3.2 | 1.9 | 1.2 | 1.2 |  | Ps | 67 | 19 | 5 | 2 | 2 |  | Lw(A) | 47 | 30 | <20 | <20 | <20 |  | 400 |  | H= | 2.7 |  |  |  | 0.56 | 0.44 | 0.37 | 0.38 | 0.31 | 0.26 | 0.29 | 0.24 | 0.2 | 0.29 | 0.24 | 0.2 |  | Vz | H= | 3.2 |  |  |  | 0.46 | 0.38 | 0.33 | 0.32 | 0.27 | 0.24 | 0.24 | 0.2 | 0.18 | 0.24 | 0.2 | 0.18 |  |  | H= | 3.8 |  |  |  | 0.38 | 0.33 | 0.29 | 0.27 | 0.24 | 0.21 | 0.2 | 0.18 | 0.16 | 0.2 | 0.18 | 0.16 |  | Vk |  | 3.7 | 2.4 | 1.6 | 1.6 |  | X0,25 |  | 4.7 | 2.9 | 1.9 | 1.9 |  | Ps |  | 33 | 9 | 4 | 4 |  | Lw(A) |  | 39 | 21 | <20 | <20 |  | 500 |  | H= | 2.7 |  |  |  | 0.69 | 0.54 | 0.46 | 0.46 | 0.38 | 0.32 | 0.37 | 0.3 | 0.25 | 0.37 | 0.3 | 0.25 |  | Vz | H= | 3.2 |  |  |  | 0.56 | 0.47 | 0.41 | 0.39 | 0.33 | 0.29 | 0.31 | 0.26 | 0.22 | 0.31 | 0.26 | 0.22 |  |  | H= | 3.8 |  |  |  | 0.47 | 0.41 | 0.36 | 0.33 | 0.29 | 0.26 | 0.26 | 0.22 | 0.2 | 0.26 | 0.22 | 0.2 |  | Vk |  | 4.6 | 3 | 2 | 2 |  | X0,25 |  | 6.4 | 4 | 2.7 | 2.7 |  | Ps |  | 51 | 14 | 6 | 6 |  | Lw(A) |  | 45 | 28 | <20 | <20 |  | 600 |  | H= | 2.7 |  |  |  |  |  |  | 0.54 | 0.44 | 0.38 | 0.45 | 0.36 | 0.3 | 0.45 | 0.36 | 0.3 |  | Vz | H= | 3.2 |  |  |  |  |  |  | 0.45 | 0.39 | 0.34 | 0.37 | 0.31 | 0.27 | 0.37 | 0.31 | 0.27 |  |  | H= | 3.8 |  |  |  |  |  |  | 0.39 | 0.34 | 0.31 | 0.31 | 0.27 | 0.24 | 0.31 | 0.27 | 0.24 |  | Vk |  |  | 3.6 | 2.4 | 2.4 |  | X0,25 |  |  | 5.2 | 3.6 | 3.6 |  | Ps |  |  | 20 | 9 | 9 |  | Lw(A) |  |  | 34 | 23 | 23 |  | 800 |  | H= | 2.7 |  |  |  |  |  |  | 0.7 | 0.57 | 0.49 | 0.61 | 0.48 | 0.41 | 0.61 | 0.48 | 0.41 |  | Vz | H= | 3.2 |  |  |  |  |  |  | 0.59 | 0.5 | 0.44 | 0.5 | 0.42 | 0.36 | 0.5 | 0.42 | 0.36 |  |  | H= | 3.8 |  |  |  |  |  |  | 0.5 | 0.44 | 0.39 | 0.42 | 0.36 | 0.33 | 0.42 | 0.36 | 0.33 |  | Vk |  |  | 4.8 | 3.2 | 3.2 |  | X0,25 |  |  | 7.9 | 5.6 | 5.6 |  | Ps |  |  | 35 | 15 | 15 |  | Lw(A) |  |  | 43 | 32 | 32 |  | 1000 |  | H= | 2.7 |  |  |  |  |  |  |  |  |  | 0.76 | 0.61 | 0.52 | 0.76 | 0.61 | 0.52 |  | Vz | H= | 3.2 |  |  |  |  |  |  |  |  |  | 0.63 | 0.53 | 0.46 | 0.63 | 0.53 | 0.46 |  |  | H= | 3.8 |  |  |  |  |  |  |  |  |  | 0.53 | 0.46 | 0.41 | 0.53 | 0.46 | 0.41 |  | Vk |  |  |  | 4 | 4 |  | X0,25 |  |  |  | 8 | 8 |  | Ps |  |  |  | 24 | 24 |  | Lw(A) |  |  |  | 39 | 39 | 
 Symbols and specifications
        Q = Air Volume in m³/hAk = Effective surface (free area) in m²B = Distance between diffusers in mH = Installation height of the diffusers in mVz = Maximum velocity at the occupied zone regarding distance between diffusers and installation height in m/sVk = Average effective velocity through the grill in m/sX0.25 = Throw length in m at an endvelocity Vt of 0,25m/sPs = Static pressure loss given in PaLw(A) = Acoustic power in dB(A)
 
 The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.The pressure losses Ps are given for grilles without damper of with fully opened damper.The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.For all special requirements, please contact our engineering office.