Standard rectangular sound attenuators with a fixed length of 1000 mm.
Delivery
possible within a week.
       
                      
        BTH-B2E  BXHXL / d= 100 / n= ... 
 
Explanation
BTH-B2E : Silencer type with B2 Splitters with cellulose foil and sheet steel plates
BXHXL : Width X Height X Length
 
d=100 : Splitter thickness of 100mm
 
n= ... : Number of splitters
 
       
              
      
      
        
                                    
                                    
                                                  Attenuation values BTH-B2 Splitter thickness d=100mm
    
      |
 |
 |
 | 40 | 8 | 16 | 24 | 28 | 25 | 23 | 18 | 15 |  | 50 | 7 | 12 | 20 | 26 | 24 | 21 | 16 | 13 |  | 60 | 6 | 10 | 18 | 24 | 23 | 19 | 14 | 11 |  | 62.5 | 6 | 10 | 18 | 24 | 23 | 19 | 14 | 11 |  | 66.7 | 6 | 9 | 17 | 24 | 23 | 19 | 14 | 11 |  | 75 | 5 | 8 | 15 | 23 | 23 | 19 | 14 | 10 |  | 80 | 4 | 8 | 15 | 22 | 23 | 19 | 13 | 9 |  | 83.3 | 4 | 8 | 15 | 22 | 23 | 19 | 13 | 9 |  | 87.5 | 4 | 7 | 14 | 22 | 23 | 19 | 13 | 9 |  | 90 | 3 | 7 | 13 | 21 | 23 | 19 | 13 | 8 |  | 100 | 3 | 6 | 12 | 21 | 23 | 19 | 13 | 8 |  
       
                                          Specifications
          
        
- L = Length in mm
 
- s = Distance between splitters in mm
 
- Hz = Frequency band in Hertz
 
- Sound attenuation capacities D given in dB
         
                                              Pressure losses BTH-B2 Splitter thickness d=100mm
    
      |
 |
 |
 | 40 | 2 | 8 | 18 | 32 | 50 | 72 | 97 | 127 | 161 | 199 |  | 50 | 2 | 7 | 15 | 27 | 43 | 61 | 84 | 109 | 138 | 171 |  | 60 | 2 | 6 | 14 | 24 | 38 | 54 | 74 | 96 | 122 | 150 |  | 62.5 | 1 | 6 | 13 | 24 | 37 | 54 | 73 | 96 | 121 | 150 |  | 66.7 | 1 | 6 | 13 | 23 | 36 | 51 | 70 | 91 | 115 | 142 |  | 75 | 1 | 5 | 12 | 21 | 32 | 46 | 63 | 82 | 104 | 129 |  | 80 | 1 | 5 | 11 | 20 | 31 | 44 | 60 | 79 | 100 | 123 |  | 83.3 | 1 | 5 | 11 | 20 | 31 | 44 | 60 | 79 | 100 | 123 |  | 87.5 | 1 | 5 | 11 | 19 | 30 | 43 | 58 | 76 | 96 | 118 |  | 90 | 1 | 5 | 10 | 18 | 28 | 41 | 56 | 73 | 92 | 114 |  | 100 | 1 | 4 | 10 | 17 | 26 | 38 | 52 | 68 | 86 | 106 |  
       
                                          Specifications
          
        - L = Length in mm
 - s = Distance between splitters in mm
 - Vs = Air velocity between splitters in m/s
 - Pressure drop vallues Dp are given in Pa
         
                                                  
    
                                          Specifications
          
        - B X H X L = Width X Height X Length in mm
 - d= Splitter thickness 100 in mm
 - n = Number of splitters
 - s = Distance between splitters in mm
         
                           |