PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

MVX-DX • Direct expansion coil module

  • Cooling modules
  • DX-cooling module
  • 25mm insulation

Direct expansion coil module

Composition

  • Battery with copper tubes and aluminium fins, mounted on sliding rails - Suitable for R32 and R410A
  • Integrated drop separator (separator pressure loss see curves). See the datasheet MVX-BF for the pressure loss graph
  • Integrated condensation tray mounted on sliding rails
  • Positioning of the module: horizontal
  • Supplied as a separate component, unmounted; factory mounted upon request
  • Outer panel: pre-painted sheet steel (RAL 9007) with protective film

Connections of the battery

  • Intake: male, by welding (expansion valve not supplied)
  • Exhaust: male tube, welding
  • Condensates: hydraulic mail piping in steel tube at gas thread
  • Connection side: on the right, in the sense of the air flow direction (on the left on request)

Selection table

TypeV [l]IN ["]OUT ["]
MVX-DX 411/25/8
MVX-DX 51.93/41 1/8
MVX-DX 63.13/41 1/8
MVX-DX 74.67/81 3/8
MVX-DX 87.21 1/81 5/8
MVX-DX 910.61 1/81 5/8
Gelieve steeds te vertrekken met de aansluitmaat van de buitenunit en rekening te houden met de totale lengte van de geïnstalleerde koelleidingen.
Veuillez toujours considérer le diamètre de raccordement de l’unité intérieure et tenir compte de la longueur totale de la tuyauterie frigorifique de l’installation.
Be sure to always start with the connection diameter of the outdoor unit and take into account the total length of the installed tubes.

Approximate volume of batteries with 1/4 in the liquid phase and 3/4 in the gaseous phase

Selection table cooling

 Tev [°C]Ta,i/RH [°C/%]*Qv,a [m³/h]
400600800100012001300-
∆P [Pa]20385985112123
MVX-DX 4732/40P [kW]/ Ta,o - RH [°C - %]3.37/14.6-824.08/17.0-784.47/18.7-764.62/20.0-754.58/21-744.6/21.5-75-
Qv,R410A [l/h] / Dp,R410A [kPa]68/10.782/15.290/17.993/18.993/18.693/19-
27/50P [kW]/ Ta,o - RH [°C - %]2.72/13.5-863.28/15.5-833.6/16.8-823.73/17.8-813.73/18.6-803.69/19.0-80-
Qv,R410A [l/h] / Dp,R410A [kPa]55/7.366/10.273/12.175/12.975/12.975/12.9-
25/50P [kW]/ Ta,o - RH [°C - %]2.23/13.0-852.63/14.8-832.83/16.0-812.86/16.9-812.89/17.6-792.99/17.9-77-
Qv,R410A [l/h] / Dp,R410A [kPa]45/5.153/6.957/7.858/858/8.160/8.7-
532/40P [kW]/ Ta,o - RH [°C - %]3.77/13.2-824.64/15.8-795.17/17.7-775.45/19.0-755.53/20.2-745.51/20.6-74-
Qv,R410A [l/h] / Dp,R410A [kPa]76/13.994/20.2105/24.6110/27112/27.7112/27.5-
27/50P [kW]/ Ta,o - RH [°C - %]3.12/12.1-863.84/14.2-844.29/15.7-824.55/16.9-814.66/17.7-804.67/18.1-80-
Qv,R410A [l/h] / Dp,R410A [kPa]63/9.978/14.387/17.592/19.595/20.495/20-
25/50P [kW]/ Ta,o - RH [°C - %]2.63/11.6-863.19/13.5-833.52/14.9-823.67/15.9-813.7/16.7-803.68/17.1-80-
Qv,R410A [l/h] / Dp,R410A [kPa]53/7.365/10.371/12.374/13.375/13.475/13.3-
 Tev [°C]Ta,i/RH [°C/%]*100012001400160018002000
∆P [Pa]567696118139162
MVX-DX 5732/40P [kW]/ Ta,o - RH [°C - %]8.1/15-828.92/16-819.45/16.9-809.83/17.8-7910.1/18.5-7810.2/19.2-77-
Qv,R410A [l/h] / Dp,R410A [kPa]162/12.9180/15.5190/17.3198/18.5203/19.4206/19.9-
27/50P [kW]/ Ta,o - RH [°C - %]6.59/13.7-867.14/14.7-857.57/15.4-847.88/16.1-838.09/16.7-838.21/17.2-82-
Qv,R410A [l/h] / Dp,R410A [kPa]133/9144/10.4152/11.6159/12.4163/13166/13.4-
25/50P [kW]/ Ta,o - RH [°C - %]5.37/13.2-865.76/14-856.04/14.7-846.22/15.3-836.32/15.9-836.34/16.3-82-
Qv,R410A [l/h] / Dp,R410A [kPa]108/6.2116/7.1122/7.7125/8.1127/8.3128/8.4-
532/40P [kW]/ Ta,o - RH [°C - %]9.21/13.4-8310.1/14.7-8110.8/15.7-8011.3/16.6-7911.7/17.4-7812/18.1-77-
Qv,R410A [l/h] / Dp,R410A [kPa]187/17.5204/20.6218/23.2229/25.3237/26.9243/28.1-
27/50P [kW]/ Ta,o - RH [°C - %]7.6/12.3-878.32/13.4-868.89/14.2-859.34/14.9-849.69/15.6-839.95/16.1-83-
Qv,R410A [l/h] / Dp,R410A [kPa]154/12.3168/14.5180/16.4189/17.9196/19.1202/20.1-
25/50P [kW]/ Ta,o - RH [°C - %]6.39/11.8-866.94/12.7-857.36/13.5-847.68/14.2-837.91/14.8-838.06/15.3-82-
Qv,R410A [l/h] / Dp,R410A [kPa]129/9141/10.5149/11.7156/12.6160/13.3163/13.7-
 Tev [°C]Ta,i/RH [°C/%]*140018002200260030003200
∆P [Pa]466894121149163
MVX-DX 6732/40P [kW]/ Ta,o - RH [°C - %]12.3/13.9-8314/15.5-8115.2/16.8-8015.9/17.8-7916.4/18.7-7816.5/19.1-77-
Qv,R410A [l/h] / Dp,R410A [kPa]249/12.9282/16.1305/18.6321/20.4331/21.5333/21.8-
27/50P [kW]/ Ta,o - RH [°C - %]9.93/13-8711.2/14.3-8512.1/15.3-8412.8/16.1-8313.2/16.8-8313.3/17.1-82-
Qv,R410A [l/h] / Dp,R410A [kPa]200/8.7226/10.8245/12.5258/13.7266/14.5268/14.7-
25/50P [kW]/ Ta,o - RH [°C - %]8.15/12.5-869.1/13.7-859.73/14.6-8410.1/15.4-8310.3/16-8310.3/16.3-82-
Qv,R410A [l/h] / Dp,R410A [kPa]164/6.1183/7.4196/8.4204/9207/9.3208/9.3-
532/40P [kW]/ Ta,o - RH [°C - %]13.8/12.5-8415.7/14.2-8217.2/15.5-8018.3/16.7-7919.1/17.6-7819.3/18.1-77-
Qv,R410A [l/h] / Dp,R410A [kPa]279/16.6319/21.1349/24.9371/27.8386/29.9392/30.7-
27/50P [kW]/ Ta,o - RH [°C - %]11.4/11.5-8813/12.9-8613/12.9-8615.2/15-8415.8/15.7-8316.1/16.1-83-
Qv,R410A [l/h] / Dp,R410A [kPa]230/11.8263/15263/15307/19.8321/21.4326/22-
25/50P [kW]/ Ta,o - RH [°C - %]9.61/11.1-8710.9/12.4-8511.8/13.4-8412.5/14.2-8312.9/14.9-8313.1/15.2-82-
Qv,R410A [l/h] / Dp,R410A [kPa]195/8.7220/10.9239/12.6253/13.9262/14.8264/15.1-
 Tev [°C]Ta,i/RH [°C/%]*2000250030003500400045004700
∆P [Pa]415979102126152160
MVX-DX 7732/40P [kW]/ Ta,o - RH [°C - %]18.2/13.5-8420.5/14.9-8222.2/16-8023.5/17-7924.4/17.9-7825/18.6-7825.1/18.9-77
Qv,R410A [l/h] / Dp,R410A [kPa]385/17.7432/21.8469/25.3496/28515/29.9527/31.2530/31.5
27/50P [kW]/ Ta,o - RH [°C - %]14.7/12.6-8716.5/13.7-8617.9/14.7-8519/15.4-8419.7/16.1-8320.2/16.7-8320.4/16.9-82
Qv,R410A [l/h] / Dp,R410A [kPa]311/12348/14.8378/17.1400/19416/20.3426/21.3429/21.6
25/50P [kW]/ Ta,o - RH [°C - %]12.2/12.2-8713.5/13.2-8514.5/14-8415.2/14.7-8415.6/15.3-8315.9/15.9-8315.9/16.1-82
Qv,R410A [l/h] / Dp,R410A [kPa]256/8.5285/10.3306/11.7320/12.7330/13.4335/13.8336/13.8
532/40P [kW]/ Ta,o - RH [°C - %]20.3/12.0-8522.9/13.5-8325/14.8-8126.7/15.8-8027.9/16.8-7928.8/17.6-7829.1/17.9-78
Qv,R410A [l/h] / Dp,R410A [kPa]429/22.6486/28.3531/33.2566/37.2592/40.4612/42.8617/43.5
27/50P [kW]/ Ta,o - RH [°C - %]16.8/11.1-8819/12.4-8720.8/13.4-8522.2/14.2-8423.3/15.0-8424.1/15.6-8324.3/15.9-83
Qv,R410A [l/h] / Dp,R410A [kPa]356/16.1403/20.1440/23.6470/26.6493/29511/30.9516/31.5
25/50P [kW]/ Ta,o - RH [°C - %]14.2/10.7-8716/11.8-8617.4/12.8-8518.4/13.5-8419.2/14.2-8319.7/14.8-8319.9/15.0-82
Qv,R410A [l/h] / Dp,R410A [kPa]302/12339/14.8368/17.1390/19407/20.5418/21.6422/21.9
 Tev [°C]Ta,i/RH [°C/%]*300040005000600070007400
∆P [Pa]386189119151162
MVX-DX 8732/40P [kW]/ Ta,o - RH [°C - %]28/13.1-8432.6/15-8235.8/16.4-8038/17.6-7939.3/18.5-7839.6/18.9-77-
Qv,R410A [l/h] / Dp,R410A [kPa]564/19.4657/25.4722/30.2766/33.6792/35.6797/36.1-
27/50P [kW]/ Ta,o - RH [°C - %]22.6/12.3-8826.3/13.8-8628.9/14.9-8430.8/15.8-8331.9/16.6-8332.2/16.9-82-
Qv,R410A [l/h] / Dp,R410A [kPa]456/13.2530/17.3583/20.5620/22.9643/24.5649/24.9-
25/50P [kW]/ Ta,o - RH [°C - %]18.7/11.9-8721.5/13.2-8523.4/14.3-8424.5/15.1-8325.1/15.8-8325.1/15.8-83-
Qv,R410A [l/h] / Dp,R410A [kPa]378/9.4434/12471/14495/15.3506/15.9506/15.9-
532/40P [kW]/ Ta,o - RH [°C - %]31/11.7-8536.4/13.6-8240.4/15.2-8043.3/16.4-7945.2/17.5-7845.7/17.9-78-
Qv,R410A [l/h] / Dp,R410A [kPa]628/24.6738/32.9819/39.8877/45916/48.7927/49.7-
27/50P [kW]/ Ta,o - RH [°C - %]25.7/10.8-8930.2/12.4-8633.6/13.7-8536.1/14.7-8437.8/15.6-8338.4/15.9-83-
Qv,R410A [l/h] / Dp,R410A [kPa]521/17.6612/23.5680/28.5731/32.4766/35.3777/36.2-
25/50P [kW]/ Ta,o - RH [°C - %]21.9/10.4-8825.5/11.9-8628.1/13--8429.9/14-8331.1/14.7-8331.4/15-82-
Qv,R410A [l/h] / Dp,R410A [kPa]443/13.1516/17.3568/20.6605/23.1630/24.7636/25.2-
 Tev [°C]Ta,i/RH [°C/%]*60007000800090001000011000
∆P [Pa]6482101122145172
MVX-DX 9732/40P [kW]/ Ta,o - RH [°C - %]48.5/15.0-8251.9/16.0-8054.5/16.9-7956.4/17.6-7957.8/18.3-7858.6/18.9-77-
Qv,R410A [l/h] / Dp,R410A [kPa]978/261046/29.31099/321137/34.11164/35.61180/36.5-
27/50P [kW]/ Ta,o - RH [°C - %]39.2/13.9-8641.9/14.6-8544.1/15.3-8445.7/15.9-8346.9/16.4-8347.7/16.9-82-
Qv,R410A [l/h] / Dp,R410A [kPa]790/17.7845/19.9888/21.8921/23.3945/24.4961/25.1-
25/50P [kW]/ Ta,o - RH [°C - %]32/13.3-8534/14.0-8435.4/14.6-8436.4/15.2-8337.1/15.6-8337.3/16.1-82-
Qv,R410A [l/h] / Dp,R410A [kPa]646/12.3685/13.7714/14.7734/15.5747/16752/16.2-
532/40P [kW]/ Ta,o - RH [°C - %]54.2/13.7-8258.4/14.8-8161.7/15.7-8064.3/16.5-7966.3/17.3-7867.7/17.9-77-
Qv,R410A [l/h] / Dp,R410A [kPa]1099/33.71183/38.41250/42.513.3/45.81343/48.31372/50.2-
27/50P [kW]/ Ta,o - RH [°C - %]45/12.5-8648.5/13.4-8551.3/14.1-8453.6/14.8-8455.4/15.4-8356.8/15.9-83-
Qv,R410A [l/h] / Dp,R410A [kPa]912/24982/27.51040/30.51086/331123/351151/36.6-
25/50P [kW]/ Ta,o - RH [°C - %]37.9/12.0-8640.6/12.7-8542.7/13.4-8444.4/14-8345.6/14.6-8346.5/15.1-82-
Qv,R410A [l/h] / Dp,R410A [kPa]768/17.6823/19.9866/21.9899/23.4924/24.6942/25.5-

Selection table heating

 Tev [°C]Ta,i [°C]Qv,a [m³/h]Qv,a [m³/h]
400600800100012001300
∆P [Pa]20385985112123
MVX-DX 44011P [kW]3.194.1855.76.326.6
Ta,o [°C]34.231.229.127.526.325.7
15P [kW]2.723.554.244.845.365.6
Ta,o [°C]3532.530.629.328.227.7
 Tev [°C]Ta,i [°C]Qv,a [m³/h]100012001400160018002000
 ∆P [Pa]567696118139162
MVX-DX 54011P [kW]7.858.859.7710.611.412.1
Ta,o [°C]33.832.431.330.329.428.6
15P [kW]6.77.58.399.710.3
Ta,o [°C]34.733.532.531.0630.830.2
 Tev [°C]Ta,i [°C]Qv,a [m³/h]140018002200260030003200
 ∆P [Pa]466894121149163
MVX-DX 64011P [kW]11.513.615.517.218.719.4
Ta,o [°C]34.83331.530.229.128.6
15P [kW]9.7811.613.214.615.916.5
Ta,o [°C]35.63432.631.530.630.2
 Tev [°C]Ta,i [°C]Qv,a [m³/h]200025003000350040004500
 ∆P [Pa]415979102126152
MVX-DX 74011P [kW]16.819.622.124.426.428.3
Ta,o [°C]35.433.832.431.230.229.3
15P [kW]14.316.718.820.722.424.1
Ta,o [°C]36.134.733.532.431.630.8
 Tev [°C]Ta,i [°C]Qv,a [m³/h]300040005000600070007400
 ∆P [Pa]386189119151162
MVX-DX 84011P [kW]25.731.336.240.544.345.8
Ta,o [°C]35.933.73230.629.429
15P [kW]21.926.730.834.437.738.9
Ta,o [°C]36.634.733.231.930.930.5
 Tev [°C]Ta,i [°C]Qv,a [m³/h]60007000800090001000011000
 ∆P [Pa]6482101122145172
MVX-DX 94011P [kW]46.551.455.96063.967.4
Ta,o [°C]33.532.331.330.429.528.8
15P [kW]39.643.747.55154.357.3
Ta,o [°C]34.533.432.531.73130.4

  • Tev = Evaporation temperature R410A
  • Ta,i = Temperature air before the coil
  • P = Total power
  • Ta,o = Temperature air after the coil
  • RH = Relative humidity
  • Qv,R410A = Flow refrigerant R410A
  • Dp, R410A = Pressure loss refrigerant R410A

Dimensions

 

A [mm]

B [mm]

C [mm]

G [mm]

I [mm]

J [mm]

K [mm]

L [mm]

M [mm]

ØUE [mm]

ØUS [mm]

ØW [mm]

[kg]

MVX-DX 4

44554544511510513590757512161/232

MVX-DX 5

5455455459514013090757518281/240

MVX-DX 6

64564564513517513590757518281/255

MVX-DX 7

74574574513515514095757522351/277

MVX-DX 8

845845970145185150110757528421/2107
MVX-DX 99459451170145175150110757528421/2140