Selection curves
EPB values
|
| AmberAir Compact CXP-4 | 2992 | 79 | 1729 |
Q = Flow rate ŋ t,epb = Thermal efficiency EPB Pelec,epb = Total electric power EPB
Technical data
|
| Main power supply | | [50Hz/VAC] | 1 x 230 | 1 x 230 | 1 x 230 | | Heating battery | Electric power | [kW] | - | 3,6 | - | | EC Fans | Power supply | [50Hz/VAC] | 1 x 230 | 1 x 230 | 1 x 230 | | Extraction fan | Power/current | [kW/A] | 0,38/2,50 | 0,38/2,50 | 0,38/2,50 | | Extraction fan | Fan speed | [rpm] | 3370 | 3370 | 3370 | | Supply fan | Power/current | [kW/A] | 0,38/2,50 | 0,38/2,50 | 0,38/2,50 | | Supply fan | Fan speed | [rpm] | 3370 | 3370 | 3370 | | Max. absorbed power/current | | [kW/A] | 0,813/5,22 | 4,41/20,90 | 0,813/5,22 | | Automatic defrost | | | integrated | integrated | integrated | | Thermal insulation | | [mm] | 50 | 50 | 50 | | | |
| Main power supply | | [50Hz/VAC] | 1 x 230 | 3 x 400 | 1 x 230 | | Heating battery | Electric power | [kW] | - | 6,0 | - | | EC Fans | Power supply | [50Hz/VAC] | 1 x 230 | 1 x 230 | 1 x 230 | | Extraction fan | Power/current | [kW/A] | 0,76/3,80 | 0,76/3,80 | 0,76/3,80 | | Extraction fan | Fan speed | [rpm] | 3530 | 3530 | 3530 | | Supply fan | Power/current | [kW/A] | 0,76/3,80 | 0.76/3.80 | 0.76/3.80 | | Supply fan | Fan speed | [rpm] | 3530 | 3530 | 3530 | | Max. absorbed power/current | | [kW/A] | 1,61/8,00 | 6,85/16,70 | 1,61/8,00 | | Automatic defrost | | | integrated | integrated | integrated | | Thermal insulation | | [mm] | 50 | 50 | 50 | | | |
| Main power supply | | [50Hz/VAC] | 3 x 400 | 3 x 400 | 3 x 400 | | Heating battery | Electric power | [kW] | - | 9,0 | - | | EC Fans | Power supply | [50Hz/VAC] | 3 x 400 | 3 x 400 | 3 x 400 | | Extraction fan | Power/current | [kW/A] | 1,05/1,60 | 1,05/1,60 | 1,05/1,60 | | Extraction fan | Fan speed | [rpm] | 3400 | 3400 | 3400 | | Supply fan | Power/current | [kW/A] | 1,05/1,60 | 1,05/1,60 | 1,05/1,60 | | Supply fan | Fan speed | [rpm] | 3400 | 3400 | 3400 | | Max. absorbed power/current | | [kW/A] | 2,15/3,42 | 11,20/16,40 | 2,15/3,42 | | Automatic defrost | | | integrated | integrated | integrated | | Thermal insulation | | [mm] | 50 | 50 | 50 | | | |
| Main power supply | | [50Hz/VAC] | 3 x 400 | 3 x 400 | 3 x 400 | | Heating battery | Electric power | [kW] | - | 12,0 | - | | EC Fans | Power supply | [50Hz/VAC] | 3 x 400 | 3 x 400 | 3 x 400 | | Extraction fan | Power/current | [kW/A] | 1,80/2,80 | 1,80/2,80 | 1,80/2,80 | | Extraction fan | Fan speed | [rpm] | 3410 | 3410 | 3410 | | Supply fan | Power/current | [kW/A] | 1,80/2,80 | 1,80/2,80 | 1,80/2,80 | | Supply fan | Fan speed | [rpm] | 3410 | 3410 | 3410 | | Max. absorbed power/current | | [kW/A] | 3,65/5,82 | 9,45/14,50 | 3,65/5,82 | | Automatic defrost | | | integrated | integrated | integrated | | Thermal insulation | | [mm] | 50 | 50 | 50 |
Detailed technical data available on request
Note
The detailed drawings shown represent a ceiling mounted AmberAir Compact CXP-4 BC in left and right versions respectively - seen from inspection side; other detailed drawings available on request.
Dimensions
|
| CXP-1 | 1750 | 50 | 1397 | 138 | 426 | 500 | 250 | 1/2" | 1/2" | 201 | | CXP-2 | 1900 | 60 | 1850 | 123 | 440 | 700 | 300 | 1/2" | 1/2" | 290 | | CXP-3 | 1950 | 60 | 2060 | 125 | 440 | 750 | 300 | 1/2" | 1/2" | 390 | | CXP-4 | 2250 | 60 | 2250 | 122 | 540 | 750 | 350 | 1/2" | 1/2" | 455 |
|