PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

ETERA HT/H Passive Cooling • Geothermal heat pumps

The ETERA heat pump from KRONOTERM is designed for energy-efficient and environmentally friendly heating of homes or buildings. This geothermal heat pump uses the constant temperature of the earth to efficiently generate heat for both space heating and the production of domestic hot water. Thanks to the use of geothermal energy, the ETERA heat pump provides significant energy savings and reduces CO₂ emissions. Kronoterm is also known for developing quiet heat pumps, which contributes to a comfortable indoor climate without noise pollution. The ETERA in HT/H Passive Cooling version can only heat and has a built-in passive cooling module. The ETERA PC only exists in the "Small" version of 2-9 kW.

Brand

  • KRONOTERM

Application

  • Heating: During cold months, the ETERA heat pump provides efficient heating for your home or building.​
  • Passive cooling: In the summer months, the built-in plate exchanger for passive cooling allows rooms to be cooled without compressor operation. This maintains a comfortable indoor climate.
  • Hot water production: The ETERA provides a constant supply of hot water for domestic use throughout the year.​

Characteristics

  • Long lifespan: Designed for a lifespan of up to 30 years, reducing the frequency of system replacement and contributing to sustainability.
  • Modular design: Thanks to the modular system design and standardised connections, installation and maintenance are simple and quick, and components can be easily upgraded or modernised.
  • Design and attention to detail: The ETERA looks just as sleek and stylish in real life as it does in the brochure, thanks to its smart design and neat finish.
  • Compact and quiet: The ETERA takes up less than 0.5 m² of floor space and operates with a sound pressure level of only 27 dB at 1 m, making the system barely audible.
  • High efficiency: The ETERA has a seasonal efficiency (SCOP) of 8.17 when using groundwater as the heat source, which means that for every kWh of electricity consumed, 8.17 kWh of useful heat is delivered.
  • Heat sources: Compatible with brine/water systems with both vertical and horizontal ground collectors.
  • Smart control: Equipped with the CLOUD.KRONOTERM system, allowing users, free online, to remotely control the heat pump via a mobile or web application, including setting heating and cooling schedules and monitoring energy consumption.
  • Well-regulated: At least one KT-2A controller is always required per ETERA installation. The KT-2A can function as a controller, thermostat or as a combination of controller/thermostat

Composition

Casing made of white powder-coated, galvanized steel sheets:

  • Modular design and removable heat pump module
  • Variable heating capacity
  • Adaptive heating control
  • Special anti-noise design (acoustically insulated casing, damping and vibration management)


The unit is removable (for easy transport within the home) and interchangeable (for a different capacity) and consists of:

  • DC inverter compressor
  • Evaporator
  • Condenser
  • Electronic expansion valve
  • Inverter drive of the same brand as the compressor
  • R-452B as refrigerant (GWP 676)
  • Drain valve
  • Filter dryer
  • Flow switch at the source
  • Pressure switch
  • High pressure sensor
  • Low pressure sensor
  • Temperature sensors
  • Inductors

Electrical board with built-in KSM control card (KRONOTERM System Manager):

Description KSM:

  • Basic heat pump and heating system controller
  • Operation via the KT-2A controller or the CLOUD.KRONOTERM mobile/web application
  • WEB module (for remote control via the CLOUD.KRONOTERM web application)
  • Space for an additional KSM+2 expansion module
  • Protective tubes for cables to the electrical cabinet
  • Internet connection
Functional features KSM:
  • Heat pump control
  • Control of additional heat generators (gas, oil or pellet boiler)
  • Control of submersible pumps
  • Circulation control
  • Heating of sanitary hot water
  • Thermal disinfection of sanitary hot water (anti-legionella)
  • Adaptive weather control of individual loops based on outside and room temperature
    (requirement: KT-1 or KT-2A accessory)
  • Active cooling
  • Groundwater flow measurement
  • Use of excess energy from the PV module (PV program)
  • Program for drying screed/floor screed
  • Control functions for:
    • 1x direct loop (radiators/convectors/floor heating)
    • 1x direct or mixing loop (radiators/convectors/floor heating)
    • Room temperature control with KT-1 and KT-2A; daily and weekly schedules
  • WEB module for internet connection (RJ45 connection – Ethernet)
  • BMS connection via MODBUS RS485 protocol
  • Smart-grid ready (SG ready)

Hydraulic circuit:
  • 3-way zone valve
  • Built-in 18 L expansion vessel in the heating circuit
  • Built-in 18 L expansion vessel in the source circuit
  • Circulation pump for heating
  • Circulation pump for source
  • Safety valve for heating
  • Safety valve for source
  • Flow sensor (Flow switch)
  • Pressure sensor in the heating circuit
  • Pressure sensor in the source circuit (checking filling/venting bottom collector)
  • Magnetic dirt separator + built-in mechanical dirt filter
  • Electric heating up to 2 kW (1 x 2 kW)

Preparations for installation:
  • Template for wall fixing to ensure easy pre-installation and placement without visible hydraulic pipes
  • Supplied wall bracket for pre-installation of pipes

Options

  • KT-2A Wall-mounted room thermostat with very comprehensive graphic display and controller (KSM) - MANDATORY OPTION
  • KT-1 Wall-mounted room thermostat with simple temperature setting for KSM
  • ND_KT-1 Wall-mounted connection box for KT-1 thermostat (surface-mounted instead of flush-mounted)
  • HYDRO B/1F1 200 L hot water boiler module for right-hand mounting on ETERA, without side panels. ETERA and HYDRO B form 1 unit after installation.
  • HYDRO BA/1F1 200 L hot water boiler module for stand-alone installation and hydraulic/electrical connection to ETERA, same appearance as ETERA.
  • KIT_P2P KT-1/KT-2A Kit for upgrading a 2-wire cable for connecting KT-1/2A and KSM

Versions

  • ETERA S-1 HT/H UF E PC

Order example

  • ETERA S-1 HT/H UF E PC
Explanation
ETERA = Name of the heat pump series (ETERNAL + TERA eternal heat from the earth)
S = Heating capacity range: 2–9 kW
M = Heating capacity range: 4–12 kW
L = Heating capacity range: 6–18 kW
1 = Generation of the device
HT = High Temperature (water temperatures up to 67 °C)
H = Heizung = Only heating and Passive cooling
UF = 1-phase connection 1 x 230 V
3F = 3-phase connection 3 x 400 V + N
E = Additional electrical heating
PC = Passive cooling built into the ETERA heat pump and no active cooling in that case

Specifications

ETERA Geothermal heat pumpUnitETERA S-1 HT/H UF E PC
  UF
CAPACITY ACCORDING TO NEN-EN 14511 BRINE/WATER Soil/Water (vertical or horizontal collector)
Rated heating capacity (B0/W35)kW4.5
COP (B0/W35) 4.7
Rated heating capacity (B0/W55)kW6
COP (B0/W55) 2.9
Maximum heating capacity (B0/W35)kW9.1
COP (B0/W35) 4.5
Maximum heating capacity (B0/W55)kW9
COP (B0/W55) 3
Cooling capacity (Passive)kW3-9
SEASONAL HEATING CAPACITIES ACCORDING TO NEN-EN 14825 Average climate zone
Rated heating capacity Pdesignh 35°C/55°C (B0)kW9.1/9.0
35°C/55°C with source fluid at 0°CSCOP5.45/4.04
CAPACITIES ACCORDING TO NEN-EN 14511 WATER/WATER Soil/Water (vertical or horizontal collector)
Rated heating capacity (B10/W35)kW4.5
COP (B10/W35) 6.4
Rated heating capacity (B10/W55)kW6.1
COP (B10/W55) 3.8
Maximum heating capacity (B10/W35)kW9.1
COP (B10/W35) 6.4
Maximum heating capacity (B10/W55)kW9.1
COP (B10/W55) 3.8
Cooling capacity (Passive)kW3-9
SEASONAL HEATING CAPACITIES ACCORDING TO NEN-EN 14825 Average climate zone
Rated heating capacity Pdesignh 35°C/55°C (B10)kW9.1/9.1
35°C/55°C with source fluid at 10°CSCOP7.68/5.37
Refrigerant R-452B
GWP 676
Amount of refrigerantkg1.1
Hydraulic  
Primary side (heating source) - BRINE-WATER BUILT-IN CIRCULATION PUMP (PWM)
Rated flow rate (min.-max.)*m³/h1.4-2.15
Max. available external pressure**kPa43.6
Brine pressure (min.-max.)bar0.5-3.0
Secundary side (heat emitter) - WATER BUILT-IN CIRCULATION PUMP (PWM)
Rated flow rate (min.-max.)*m³/h0.8-1.55
Max. available external pressure**kPa47.1
Primary side (heat source) - WATER-WATER BUILT-IN CIRCULATION PUMP (PWM)
Rated flow rate (min.-max.)*m³/h1.4-2.15
Min. pressure drop with MODUL_PIL ETERA***kPa18.7
Brine pressure (min.-max.)bar0.5-3.0
Secundary side (heat emitter) - WATER BUILT-IN CIRCULATION PUMP (PWM)
Rated flow rate (min.-max.)*m³/h0.8-1.55
Max. available external pressure**kPa47.1
Hot water heater 200 L in stainless steel for flush mounting/stand alone water heater HYDRO B/HYDRO BA
Volume optional buffer tank**l40
Heat loss Qst at 55°Ckwh/24h1.2
Heat loss Qst at 35°Ckwh/24h0.335
Operating range in heating  
-Min./max. temperature of fluid at source side°C-10/15
Operating range in cooling  
-Min./max. temperature of fluid at source side°C5/25
Power supplyV230V 1 50 Hz
Dimensions (L x H x D) ETERA (NET)mm600x1515x600
Weight ETERA (NET)kg189
Dimensions (L x H x D) ETERA (TRANSPORT)mm700x1655x625
Weight ETERA (TRANSPORT)kg200.5
VERSIONS  
Heat source Geothermal energy (Collector/ground water)
Heat emitter Water
Regulation KSM
Warmtepomp locatie Indoor
Position of regulation Built-in in heat pump unit
Compressor 1 Scroll with variable speed
Compressor driver DC Inverter
Expansion valve Elektronical (EEV)
Circulation pump on source side Built-in PWM
Circulation pump on secundary side Built-in PWM
Electrical heater 1 x 2 kW**
3-way valve for switching from CV to DHW Built-in
Water fow meter on heating side Built-in
Flow switch on source side Built-in
Water pressure sensor on heating side Built-in
Water pressure sensor on source side Built-in
Safety valve/pressure valve on heating side Built-in
Safety valve/pressure valve on source side Built-in
Expansion vessel 18 L on heating side Built-in
Expansion vessel 18 L on source side Built-in
Magnetic dirt separator/mechanical filter on heating side Built-in
COMMUNICATION  
BMS connection MODBUS protocol (UTP cable with RJ45 connection) RS 485
Internet connection FTP cable - RJ45 connection - Ethernet

Specifications

SOUND ACCORDING TO STANDARD EN 12102 IN OPERATING MODE B0W35UnitETERA S-1 HT/H UF E PC
SOUND POWER AS INDICATED ON THE ECOLABEL ENERGY LABEL  
Sound powerdB (A)32
Sound pressure level at 1 m distancedB (A)24
SOUND POWER IN "OPTIMAL" MODE  
Sound powerdB (A)32-43
Sound pressure level at 1 m distancedB (A)24-35
SOUND POWER IN "SILENT" MODE  
Sound powerdB (A)32-38
Sound pressure level at 1 m distancedB (A)24-30
Sound power is not related to distance, it describes the total sound energy emitted in all directions.
Sound pressure depends on the measurement location in the sound field and describes the sound pressure at that location.

Configuration

Operational limits
HELPCopyrightSales conditionsCookie policyAirvance Group