This DC inverter multi-split system combines high efficiency with energy-saving operation. Thanks to the outdoor unit and a maximum piping length of up to 80 m (40 m of which is pre-charged), installation is extremely flexible, even in complex situations.
With a single system, you can cool or heat up to three rooms. Moreover, the unit simultaneously provides domestic hot water (DHW). In summer, it intelligently utilizes the "free" heat extracted from the cooled rooms, a sustainable solution that perfectly combines comfort and savings.
Combination opportunities
|
| Basic wall models | R4LW 09 VIVA | x | | R4LW 12 VIVA | x | | R4LW 18 VIVA | x | | R4LW 24 VIVA | x | | Design wall models | R4LW 09 ONYX | x | | R4LW 12 ONYX | x | | R4LW 18 ONYX | x | | R4LW 24 ONYX | x | | Floor models | R4LF 09 TERRA | x | | R4LF 12 TERRA | x | | R4LF 18 TERRA | x |
Specifications
|
| Data according to standard combination | | 9+9+9+SWW | | Cooling capacity (min. - nom. - max.)** | kW | 2.6 - 10.6 - 12.0 | | Heating capacity (min. - nom. - max.)** | kW | 3.0 - 12.0 - 14.0 | | (Max.) heating capacity at -7°C (outdoor @ 20°C (indoor) | kW | 8.2 | | Absorbed power (rated) (C/H) | kW | 3.0/3.2 | | EER (Cooling) | | 3.66 | | COP (Heating) | | 3.75 | | Pdesign (C/H)*** | kW | 10.6/10.5 | | SEER (Cooling) | | 7.2 | | SCOP (Heating) | | 4.2 | | Energy class (C/H) | | A++/A+ | | Absorbed current (rated) (C/H) | A | 13.0/14.0 | | Annual energy consumption (C/H) | kWh/j | 515/3500 | | Sound pressure level | dB(A) | 60 | | Sound power level | dB(A) | 70 | | Air flow rate (maximum) | m³/h | 5800 | | Dimensions (H x W x D) | mm | 826x1020x427 | | Weight | kg | 72 | | Compressor inverter type | | DC Twin Rotary | | Cooling pipes | inch | 4x 1/4 - 3/8 | | Maximum length/height of cooling pipes | m/m | 80/15 | | Maximum length of cooling pipes per indoor unit | m | 20 | | Minimum length of cooling pipes per indoor unit | m | 3 | | Refrigerant | | R32 (675) | | Amount of pre-charged refrigerant | g (CO2eq-T) | 2400 (1.62) | | Number of prefilled meters | m | 40 | | Extra amount of refrigerant per meter | g/m | 20 | | Operating temperature in cooling mode | °C | -15~+43 | | Operating temperature in heating mode | °C | -22~+24 | | Power supply | V | 230/1 | | Power supply cable section | mm² | 3G 6 | | Automatic fuse (slow) | A | 32 | | * Specifications and design are subject to change for further improvement without prior notice. | | ** Cooling and heating capacities are achieved under the following conditions: | | (Cooling) Indoor temp.: 27°C D.B./19°C W.B. - Outdoor temp.: 35°C D.B./24°C W.B. | | (Heating) Indoor temp.: 20°C D.B. - Outdoor temp.: 7°C D.B./6°C W.B. | | *** Pdesign is the cooling and heating capacity at the design temperature 35°C (C) and for the average climate zone at -10°C (H) | | COP/EER according to EN14511 - SCOP/SEER according to EN14825 - sound power according to EN12102 | | Refrigeration adapter pieces supplied with outdoor unit |
Combination tables
|
|
|
| 2 rooms | 9 | 9 | - | - | 18 | 2.6 | 2.6 | - | - | 5.2 (2.4 - 5.8) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 9 | 12 | - | - | 21 | 2.6 | 3.5 | - | - | 6.1 (2.4 - 6.8) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 9 | 18 | - | - | 27 | 2.6 | 5.0 | - | - | 7.6 (2.4 - 8.4) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 9 | 24 | - | - | 33 | 2.6 | 7.2 | - | - | 9.8 (2.4 - 10.9) | 2.6 (1.6 - 3.6) | 7.2 | A++ | | 12 | 12 | - | - | 24 | 3.5 | 3.5 | - | - | 7.0 (2.4 - 7.8) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 12 | 18 | - | - | 30 | 3.5 | 5.0 | - | - | 8.5 (2.4 - 9.4) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 12 | 24 | - | - | 36 | 3.5 | 5.0 | - | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.0) | 7.2 | A++ | | 18 | 18 | - | - | 36 | 5.3 | 5.3 | - | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.0) | 7.2 | A++ | | 18 | 24 | - | - | 42 | 4.5 | 6.0 | - | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.0) | 7.2 | A++ | | 24 | 24 | - | - | 48 | 5.3 | 5.3 | - | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.0) | 7.2 | A++ | | 3 rooms | 9 | 9 | 9 | - | 27 | 2.6 | 2.6 | 2.6 | - | 7.8 (2.4 - 8.6) | 2.4 (1.6 - 3.5) | 7.2 | A++ | | 9 | 9 | 12 | - | 30 | 2.6 | 2.6 | 4.2 | - | 9.4 (2.4 - 10.4) | 2.6 (1.6 - 3.6) | 7.2 | A++ | | 9 | 9 | 18 | - | 36 | 2.6 | 2.6 | 5.3 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 9 | 24 | - | 42 | 2.3 | 2.3 | 6.0 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 12 | 12 | - | 33 | 2.6 | 3.5 | 3.5 | - | 9.6 (2.4 - 10.6) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 12 | 18 | - | 39 | 2.4 | 3.2 | 4.9 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 12 | 24 | - | 45 | 2.1 | 2.8 | 5.6 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 18 | 18 | - | 45 | 2.1 | 4.2 | 4.2 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 9 | 18 | 24 | - | 51 | 1.9 | 3.7 | 4.9 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 12 | 12 | 12 | - | 36 | 3.5 | 3.5 | 3.5 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 12 | 12 | 18 | - | 42 | 3.0 | 3.0 | 4.5 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 12 | 12 | 24 | - | 48 | 2.6 | 2.6 | 5.3 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 12 | 18 | 18 | - | 48 | 2.6 | 3.9 | 3.9 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 12 | 18 | 24 | - | 54 | 2.3 | 3.5 | 4.7 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | | 18 | 18 | 18 | - | 54 | 3.5 | 3.5 | 3.5 | - | 10.6 (2.4 - 12.0) | 3.0 (1.6 - 4.6) | 7.2 | A++ | |
|
|
| 2 rooms | 9 | 9 | - | - | 18 | 2.8 | 2.8 | - | - | 5.6 (3.0 - 14.0) | 2.2 (1.6 - 3.1) | 4.0 | A+ | | 9 | 12 | - | - | 21 | 2.8 | 3.8 | - | - | 6.6 (3.0 - 14.0) | 2.2 (1.6 - 3.1) | 4.0 | A+ | | 9 | 18 | - | - | 27 | 2.8 | 5.6 | - | - | 8.4 (3.0 - 14.0) | 2.2 (1.6 - 3.6) | 4.0 | A+ | | 9 | 24 | - | - | 33 | 2.8 | 8.5 | - | - | 11.3 (3.0 - 14.0) | 2.8 (1.6 - 5.0) | 4.0 | A+ | | 12 | 12 | - | - | 24 | 3.8 | 3.8 | - | - | 7.6 (3.0 - 14.0) | 2.2 (1.6 - 3.1) | 4.0 | A+ | | 12 | 18 | - | - | 30 | 3.8 | 5.6 | - | - | 9.4 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 24 | - | - | 36 | 3.8 | 8.2 | - | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 18 | 18 | - | - | 36 | 6.0 | 6.0 | - | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 18 | 24 | - | - | 42 | 5.1 | 6.9 | - | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 24 | 24 | - | - | 48 | 6.0 | 6.0 | - | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 3 rooms | 9 | 9 | 9 | - | 27 | 2.8 | 2.8 | 2.8 | - | 8.4 (3.0 - 14.0) | 2.2 (1.6 - 3.6) | 4.0 | A+ | | 9 | 9 | 12 | - | 30 | 2.8 | 2.8 | 3.8 | - | 9.4 (3.0 -14.0) | 2.8 (1.6 - 5.0) | 4.0 | A+ | | 9 | 9 | 18 | - | 36 | 3.0 | 3.0 | 6.0 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 9 | 9 | 24 | - | 42 | 2.6 | 2.6 | 6.9 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 9 | 12 | 12 | - | 33 | 3.2 | 4.4 | 4.4 | - | 11.3 (3.0 - 14.0) | 2.8 (1.6 - 5.0) | 4.0 | A+ | | 9 | 12 | 18 | - | 39 | 2.8 | 3.7 | 5.5 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 9 | 12 | 24 | - | 45 | 2.4 | 3.2 | 6.4 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 9 | 18 | 18 | - | 45 | 2.4 | 4.8 | 4.8 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 9 | 18 | 24 | - | 51 | 2.1 | 4.2 | 5.7 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 12 | 12 | - | 36 | 4.0 | 4.0 | 4.0 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 12 | 18 | - | 42 | 3.4 | 3.4 | 5.1 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 12 | 24 | - | 48 | 3.0 | 3.0 | 6.0 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 18 | 18 | - | 48 | 3.0 | 4.5 | 4.5 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 12 | 18 | 24 | - | 54 | 2.7 | 4.0 | 5.3 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | 18 | 18 | 18 | - | 54 | 4.0 | 4.0 | 4.0 | - | 12.0 (3.0 - 14.0) | 3.1 (1.6 - 5.0) | 4.0 | A+ | | Combinations of indoor units shown here are models of working units, not of connectable units. | | A minimum of 2 indoor units must be connected with a total of 18 kBtu. | | A maximum of 4 indoor units can be connected with a total of 54 kBtu. | | * Cooling and heating capacities are achieved under the following conditions: | | (Cooling) Indoor temp.: 27°C D.B./19°C W.B. - Outdoor temp.: 35°C D.B./24°C W.B. | | (Heating) Indoor temp.: 20°C D.B. - Outdoor temp.: 7°C D.B./6°C W.B. | | SCOP/SEER according to EN14825 |
|