The Si RD3 refrigerant leak detector uncovers leaks of most common refrigerant gases to a high degree of sensitivity, including all HCFC and HFC refrigerants, R1234yf, R1234ze, R290, R600a, and mixtures of 5% hydrogen and 95% nitrogen (Nidron 5 and Trace-A-Gas).
Application
Detection of refrigerant leaks for HCFC, HFC and forming gas (mixtures of 5% hydrogen and 95% nitrogen (Nidron 5 and Trace-A-Gas))
Specifications
Heated diode sensor
30 cm flexible probe
3 modes: Low, Normal and High
Manual and automatic autozero
Detection includes: all HCFC and HFC refrigerants, R1234yf, R1234ze, R290, R600a, and mixtures of 5% hydrogen and 95% nitrogen (Nidron 5, Trace-A-Gas)
The refrigerant leak detector complies with EN 14624 standard that determines the following points:
Minimum threshold of sensitivity: Fixed: < 1 g/year at 3 mm In moving air: 2 g/year, 2 cm/s at 3 mm
Minimum time of detection: (1 g/year): 1 second
Autozero: 2 seconds
Recuperation time after exposition: from 1 to 10 seconds (depending on detection level and threshold of sensitivity)