PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

FCA • Cleaners

  • Cleaning products
  • Hydraulic systems
  • Cleaning products

This pressurised aerosol cleaner (C3 Fast Cleaner 570915) loosens sludge, limescale deposits and dirt particles from hydraulic systems, after which the filter or dirt separator collects the dirt so that it can be removed. The cleaner can be used in new and existing heating and cooling systems at high and low temperatures. The cleaner is not aggressive and therefore suitable for all materials used in hydraulic systems. Furthermore, the cleaner can be used with all types of propylene glycol.

Brand

Caleffi

Application

To remove sludge, scale, dirt particles and deposits from existing installations. For new installations, the cleaner enables commissioning to the required standards.

Specifications

  • Aerosol spray can content: 0,4 l
    The entire content of an aerosol spray can is sufficient to treat 150 litres of installation water (approximately 15 radiators or 120 m2 of underfloor heating).
  • Colour: light brown
  • Odour: light
  • pH: 7–8
  • Relative density: 1,15
  • Solubility (in water): soluble in hot and cold water
  • There is no problem in case of overdose.
  • The temperature of the water affects the duration of the treatment. Allow to circulate for:
    • minimum 1 hour with high-temperature water (T > 50 °C)
    • minimum 4 hours with low-temperature water (30 °C < T < 40 °C)
    • up to 1 week with cold water

Notes

Flushing an existing or new installation:
Thanks to the adapter piece of the aerosol spray can, FCA can be added to the system by means of a DIRTMAG® dirt separator. To do this, proceed as follows:

! Switch off the circulation pump!

1. Drain the water from the dirt separator to remove any sediment.
2. Unscrew the hose connector of the dirt separator and tighten the spray can with the adapter piece. Open the drain tap of the dirt separator again.
3. Add FCA by pressing the button. The entire contents of the spray can are emptied in approximately twenty seconds.
4. Let the water circulate according to the schedule in the paragraph ‘Dosage’. For very dirty installations, the cleaning time must even be extended to 1 week.
5. Drain the dirt via the dirt separator until clean water is obtained. Dispose of the waste water in accordance with the applicable regulations.
6. Fill in the label on the cap of the spray can and apply it to the heat pump.

Full instructions can be found in the manual under “Downloads”.
HELPCopyrightSales conditionsCookie policyAirvance Group